Modbus for residential D24810 User manual(A007)

Thecolumn“NVM”indicatesifthevalueisstoredinanon-volatilememory(i.e.EEPROM)whenwritingto
it.
6Wiring
Fig.1Modbuswiring
PositionDescription
1
VTCunit.
2
RJ45onPCB,seenfromthetop.
3
Terminationresistor,closetotheendoftheline.
4Modbusmaster.
7Modbusvariablelist
7.1Registersforfancontrol
NameRegister
address
RorR/W
NVMAccess
(Reg./Coil)
Description/remarks
REG_FAN_SPEED_LEVEL
101
R/W
Y
1
Reg
0:Fansoff
1:Fansonlowspeed
2:Fansonnormalspeed
3:Fansonhighspeed
4:Automode
REG_FAN_SF_FLOW_LOW
102
R/W
Y
1
Reg
Supplyairfanspeedforlowspeed
REG_FAN_EF_FLOW_LOW
103
R/W
Y
1
Reg
Extractairfanspeedforlowspeed
REG_FAN_SF_FLOW_NOM
104
R/W
Y
1
Reg
Supplyairfanspeedfornominalspeed
REG_FAN_EF_FLOW_NOM
105
R/W
Y
1
Reg
Extractairfanspeedfornominalspeed
REG_FAN_SF_FLOW_HIGH
106
R/W
Y
1
Reg
Supplyairfanspeedforhighspeed
REG_FAN_EF_FLOW_HIGH
107
R/W
Y
1
Reg
Extractairfanspeedforhighspeed
ModbusforResidentialunitsUserManual
D24810
2