Modbus for residential D24810 User manual(A007)

7.10RegistersforVTCdefrosting
NameRegister
address
RorR/W
NVMAccess
(Reg./Coil)
Description/remarks
REG_DEFR_STATE_VTC
651RReg
Stateofdefrostingstatemachine.
0:Nodefrostingongoing
2:Bypassdefrosting
3:Stopdefrosting
4:Defrosterror
REG_DEFR_CONFIGURATION
652RReg
Defrostingconguration.
0:A
1:B
2:C(nolongersupportedbyPCU-EC4)
3:D(nolongersupportedbyPCU-EC4)
REG_DEFR_UNBAL_ALLOWED
653
R/W
Y
Reg+CoilCoil10433:Unbalanceallowed.
0:Unbalancenotallowed.
1:Unbalanceallowed.
REG_DEFR_MODE_VTC
654
R/W
YReg
Defrostingmode.
Allowedvalues:
IfnoRHsensorispresent:1–5.
IfRHsensorispresent:1–3,
correspondingtoSoft,Normaland
Hard.
REG_RH_SENSOR_PRESENT
655
R/W
Reg
SettingofpresenceofRHsensor.
0:Sensorisnotconnected,orthesensor
isconnectedbutshallnotbeused.
1:Sensorisconnectedandshallbeused.
7.11RegisterforVR/VTRdefrosting
NameRegister
address
RorR/W
NVMAccess
(Reg./Coil)
Description/remarks
REG_DEFR_STATE_VR
671RReg
Stateofdefrostingstatemachine.
0:Inactive
1:Lowtemperature
2:Defrosting
REG_DEFR_MODE_VR
672
R/RW
YReg
Defrostingmode.
Allowedvalues:0-5.
ModbusforResidentialunitsUserManual
D24810
11