english PXDM6A / PXDM10A Multipurpose controller for variable voltage 3 ~ fans Operating Instructions Software version: D2499A from Version 02.03 L-BAL-E180-GB 1243 Index 001 Part.-No.
Operating Instructions – model series PXDM6A / PXDM10A Content 1 General notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 Structure of the operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.2 Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.3 Exclusion of liability . . . . . . . . . . . . . . . . .
Operating Instructions – model series PXDM6A / PXDM10A 5.13.3 5.13.4 USB-interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LON® Bus system is possible via add-on module . . . . . . . . . . . . . . . . . . . . . . . . 13 13 5.14 Potential at control voltage connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 6 Controls and Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating Instructions – model series PXDM6A / PXDM10A 9.10.2 Digital inputs “D1” / “D2” . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.10.2.1 Menu overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.10.2.2 Enable ON/OFF function |1D | . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.10.2.3 External fault Function |2D | . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.10.2.
Operating Instructions – model series PXDM6A / PXDM10A 1 1.1 General notes General notes Structure of the operating instructions Before installation and start-up, read this manual carefully to ensure correct use! We emphasize that these operating instructions apply to specific units only, and are in no way valid for the complete system! Use these operating instructions to work safely with and on the device.
Operating Instructions – model series PXDM6A / PXDM10A Safety instructions Danger due to electric current Warning of dangerous voltage or dangerous current. Information Important additional information and advice for user. 2.3 Product safety The device conforms to the state of the art at the time of delivery and is fundamentally considered to be reliable.
Operating Instructions – model series PXDM6A / PXDM10A Product overview Danger due to electric current It is generally forbidden to carry out work on electrical live parts. Protection class of the device when open is IP 00! It is possible to touch hazardous voltages directly! The safe isolation from the supply must be checked using a two-pole voltage detector. Attention! Automatically restart after a power failure or mains disconnection! 2.
Operating Instructions – model series PXDM6A / PXDM10A 3.4 Storage • • • 3.5 Mounting The device must be stored in its original packaging in a dry and weather-proof room. Avoid exposure to extreme heat and cold. Avoid over-long storage periods (we recommend a maximum of one year). Disposal / recycling Disposal must be carried out professionally and environmentally friendly in accordance with the legal stipulations. 4 4.
Operating Instructions – model series PXDM6A / PXDM10A 4.4 Electrical installation Installation location for agriculture In order to avoid damage caused by ammoniac vapours, the controller shall not be installed in the stable, but rather in an outhouse wherever possible. 4.5 Temperature influences during commissioning Avoid condensation in the controller and functional faults attributable to condensation by storing the controller at room temperature! 5 5.
Operating Instructions – model series PXDM6A / PXDM10A 5.3 Electrical installation Mains connection 5.3.1 Line voltage Power from the mains is connected to terminals: PE, L1, L2, L3 and N. Here, it must be strictly observed that the mains voltage lies within the allowable tolerance specifications ( Technical data and nameplate affixed to the side). The neutral conductor connection “N” is only for the leakage currents`s reduction. It is of no significance for the fuction of the device.
Operating Instructions – model series PXDM6A / PXDM10A 5.6 Electrical installation Motor protection Motor protection is possible by connecting thermostats “TB” (thermal contacts) or thermistors “TP” (PTC). • When several motors are connected ensure that the thermal contacts “TB” or PTC resistors “TP” are always connected in series. A maximum of six individual thermistors (DIN 44081 or DIN 44082) may be connected in series to a single device.
Operating Instructions – model series PXDM6A / PXDM10A 5.10 Electrical installation Add-on module type Z-Modul-B Part-No. 380052 The expansion module can be retrofitted. This could be necessary if the analog and digital inputs and outputs are not sufficient for certain applications. The board is easy to install into the device and is connected with the control device via a plug. Program the additional inputs and outputs in “IO Setup”.
Operating Instructions – model series PXDM6A / PXDM10A Electrical installation Examples for MODBUS connection Recommended wire types 1. CAT5 / CAT7 cables 2. J-Y (St) 2x2x0.6 (telephone wire) 3. AWG22 (2x2 twisted pair) When using telephone flex with four cable cores, we recommend the following allocation: “A (D+)” = red, “B (D-)” = black, “GND” = white Information • Pay attention to sufficient distance from powerlines and motor wires (min.
Operating Instructions – model series PXDM6A / PXDM10A 6 6.1 Controls and Menu Controls and Menu Multipurpose LC display and keyboard 2 3 4 5 6 1 7 8 23.09.2011 v_display_erkl_a_u_con.vsd 1. 2. 3. 4. 5. 6. 7. 8. Numeric display 5 digit Moon-Symbol for set point 2 Alarm-Symbol (fault indication) Fire-Symbol (heating operation) STOP-Symbol (enable) Bargraph Fanlevel Text line 3 figures (display unit, etc.) Text line 16 figures (display text menu.) 6.
Operating Instructions – model series PXDM6A / PXDM10A 6.3 Controls and Menu Menu structure PIN 0010 STOP Service → → → → ← ← ← ← User ▼ ▲ Start ▼ ▲ Info Setting ▼ ▲ ▼ ▲ Events Base setup P↓ ↑ ESC P↓ ↑ ESC P↓ ↑ ESC P↓ ↑ ESC P↓ ↑ ESC PIN input E1 Actual Setpoint1 Motor fault Mode ▲▼ ▲▼ ▲▼ ▲▼ ▲▼ E2 Actual Setpoint2 E1 Analog In Menu dependent on device type Selection of the menu group (e.g. Base setup) to the right through the ▼-key, to the left through the ▼-key.
Operating Instructions – model series PXDM6A / PXDM10A 7 7.1 Base setup Base setup Select operation mode Information Simple installation is possible through the selection of the preprogrammed mode of operation. This determines the basic function of the device. The controller configuration is carried out automatically when selecting the application-specific operating modes.
Operating Instructions – model series PXDM6A / PXDM10A Base setup Mode and Signal to E1, E2 2.01 .. 2.03 GND GND 0 - 10 V KTY81-210 PT1000 E1 4.01 + 5.01 MBG..-I DSG 0 - 10 V TF.. 0 - 10 V A1 3.01 + 3.02 E1 T 24V E1 24V E1 GND T GND GND GND GND 10 k 2.04 + 2.05 1 3 BN GN WH YE MBG.. DSG.. (4 - 20 mA) (0 - 10 V) 3.03 + 3.04 TF.. KTY81-210 PT1000 BN T 24V E2 GND T GND GND 1 3 BN GN MAL 0 - 10 V 1 24V E1 GND GND 2 3 MAL1/10 (0 - 10 V) TF.. MBG..
Operating Instructions – model series PXDM6A / PXDM10A 8 8.1 Start-up Start-up Prerequisites for commissioning Attention! 1. You must mount and connect the device in accordance with the operating instructions. 2. Double check that all connections are correct. 3. The mains voltage must match the information on the rating plate. 4. The rated current on the rating plate will not be exceeded. 5. Make sure that no persons or objects are in the fan's hazardous area. 8.
Operating Instructions – model series PXDM6A / PXDM10A 9 9.1 9.1.1 Programming Programming Speed controller 1.01 Base setup 1.01 Base setup Base setup Mode Factory setting Mode: 1.01 Mode E1 Analog In E2 Function E2 Analog In 9.1.2 E1 Analog In Selection: 0 - 20 mA, 4 - 20 mA, Bus (Inverting Factory setting: 0 - 10 V IO Setup) E2 Function (only for special applications) Analog input 2 “E2” factory set at “OFF”.
Operating Instructions – model series PXDM6A / PXDM10A Programming Diagram setting signal and output voltage (Idealized principle diagram) nM 100 % Min. 0 % Max. = 100 % Min. 35 % Max. = 85 % 50 % Min. Si 0 10 1 9 2 8 3 7 4 6 5 5 6 4 7 3 0 20 4 2 18 5,6 4 16 7,2 6 14 8,8 8 12 10,4 10 10 12 12 14 16 18 8 6 4 2 13,6 15,2 16,8 18,4 20 0 20 20 18,4 16,8 15,2 13,6 12 10,4 4 8,8 8 2 7,2 9 1 5,6 10 0 0 – 10 V 10 – 0 V 0 – 20 mA 20 – 0 mA 4 – 20 mA 20 – 4 mA 09.05.
Operating Instructions – model series PXDM6A / PXDM10A Programming E2 Function (only for special applications) E2 Function • Function |1E | = External Setpoint e.g. via external signal (0 - 10 V) instead of “Setpoint1” – For sensor type “E1 Analog In” = “KTY or PT1000”: 0 - 10 V -50.0...+150 °C. – For sensors with active signal: 0 - 10 V E2 Analog In • • 0 - 100 % sensor measuring range. Function |2E | = External manual operation via external signal (0 - 10 V).
Operating Instructions – model series PXDM6A / PXDM10A Programming Pband Narrow control range = Short control times Wide control range = Longer control times and more stable control Pband Passive sensor type “KTY”, “PT1000” Setting range: 0 - 200.0 K (Kelvin) Factory setting: 5.0 K, (at 2.02 : 20.0 K) active Sensor type “MTG-120V” Setting range: -10.0...+120.0 K Factory setting: 65.0 K Min. Speed Max. Speed Manual mode Speed man. 9.2.3 Minimal Speed Setting range: 0...
Operating Instructions – model series PXDM6A / PXDM10A Programming Example 2: Temperature control in “Heating function” (Idealized principle diagram) nM 100 % Min. 0 % Max. = 100 % Max. 50 % Min. Min. 35 % Max. = 85 % I 10 °C 20 °C S 10 K R 09.05.2007 v_tempcontrol_heat_nmotor.vsd (Controller Setup: “Val > Set = n+” to “OFF”) nM Motor speed S Setpoint R Pband I Actual value 9.2.4 Additional for mode 2.03 : Signal output 0 - 10 V The 0 - 10 V output signal can, e.g.
Operating Instructions – model series PXDM6A / PXDM10A Programming Example for signal out 0 - 10 V (IO Setup: “A function” = |6A | ) 10 V 100 % Min. 0 % Max. = 100 % Min. 35 % Max. = 85 % Max. Analog Out 50 % Min. Analog Out I 20 °C S 30 °C 10 K R 09.05.2007 v_signal_ausgang_0_10_v.vsd Example: Setpoint ventilation 25.0°C, Offset -5.0 K, Pband 10.0 K S Setpoint Ventilation +/- Offset R Pband I Actual value 9.2.5 For mode 2.
Operating Instructions – model series PXDM6A / PXDM10A Programming Temperature variation with reprogramming to |10K | for “K2” in IO Setup, e.g., for activation of the Cooling Example: Setpoint 15.0 °C, Offset +5.0 K, Hysteresis 2.0 K [°C] 30 28 26 24 22 20 18 16 14 12 10 1 3 5 7 9 11 13 15 17 19 21 [min] ON 9.2.6 ON ON 23 25 27 29 16.03.2007 v_relais_kuehlen_10k_pos_offset.
Operating Instructions – model series PXDM6A / PXDM10A 9.3 9.3.1 Programming Pressure control for condensers refrigeration 3.01 ... 3.04 Base setup 3.01 ... 3.04 Base setup Base setup Mode Mode selection e.g. 3.01 Mode E1 Analog In E1 Analog In For all Modes in Group 3 ( 3.01 , 3.02 , 3.03 , ...) “E1 Analog In” factory setting to “MBG-30I”. (measuring range 0...30 bar) proportional output 4 - 20 mA Selection sensor: MBG-30I, MBG-50I, DSF2-25 Alternative selection signal: 0 - 10 V, 4 - 20 mA.
Operating Instructions – model series PXDM6A / PXDM10A 9.3.2 Programming Setting for operation modes 3.01 ... 3.04 3.01 Pressure control condensers, setting Setpoint in bar 3.02 Pressure control for condensers with input for refrigerant, Setpoint in °C 3.03 Two sensors for dual circuit condenser. Automatic regulation to the highest pressure (selection amplifier integrated) operation display: “Control value”, Setpoint in bar 3.
Operating Instructions – model series PXDM6A / PXDM10A 9.3.3 Programming Functional diagrams pressure control condensers Functional diagram for Mode 3.01 and 3.03 (Idealized principle diagram) n Motore Min. 0 % 100 % Max. = 100 % 50 % Min. Valore effettivo 12 bar Valore nominale 5 bar Campo di regolazione 17 bar 27.03.2007 v_diagramm_301_303_bar.vsd nM Motor speed S Setpoint R Pband I Actual value Functional diagram for Mode 3.02 and 3.04 (Idealized principle diagram) n Motore 100 % Min.
Operating Instructions – model series PXDM6A / PXDM10A 9.4 9.4.1 Programming Pressure control airconditioning 4.01 ... 4.03 Base setup 4.01 ... 4.03 Base setup Base setup Mode Mode selection e.g. 4.01 Mode E1 Analog In E1 Analog In In all group 2 operating modes 4 ( 4.01 , 4.02 , 4.03 , ....) “E1 Analog In” factory setting “DSG200 ”. Selection sensor type: “DSG 50”, “DSG100*”, “DSG200”, “DSG300”*, “DSG500”, “DSG1000”, “DSG2000”, “DSG4000”, “DSG6000 ” (* no standard type).
Operating Instructions – model series PXDM6A / PXDM10A 9.4.2 Programming Setting for operation modes 4.01 ... 4.03 • 4.01 pressure control, setpoint in Pa • 4.02 and 4.03 Pressure control for ventilation systems setpoint depending on outdoor temperature Setting Setting Setpoint1 Setpoint2 Pband Min. Speed Max. Speed Manual mode Speed man. L-BAL-E180-GB 1243 Index 001 Setpoint1 Setting range: in measuring range of sensor Factory setting: 100 Pa Setpoint2 Setting “Setpoint 2” e.g.
Operating Instructions – model series PXDM6A / PXDM10A Programming Additional menu item for mode 4.02 and 4.03 with outside-temperature dependent targetsetpoint. Outside-temperature dependent target-setpoint Sollwert 1 [Pa] Sollwert 2 [Pa] P-min SA [Pa] An outside temperature compensation can be activated (sensor connection “E2” = “Analog In 2”) when being operated as a pressure regulation device. An optimal building climate, e.g., can be achieved through this.
Operating Instructions – model series PXDM6A / PXDM10A Programming E1 Offset Sensor calibration with calibrated comparison device E1 Offset E2 Function E2 Function (only for special applications) • External setpoint = Function |1E | by external signal (0 - 10 V) instead of 0 - 100 % setting range “Setpoint 1”.
Operating Instructions – model series PXDM6A / PXDM10A Programming Additional menu item for mode 5.02 with outside-temperature dependent target-setpoint Outside-temperature dependent target-setpoint Sollwert 1 [m3/h] Sollwert 2 [m3/h] An outside temperature compensation can be activated (sensor connection “E2” to “Analog In 2”) when being operated as a air volume regulation device. An optimal building climate, e.g., can be achieved through this.
Operating Instructions – model series PXDM6A / PXDM10A E2 Function Programming E2 Function (only for special applications) • External setpoint = Function |1E | by external signal (0 - 10 V) instead of “Setpoint 1”. 0 - 10 V 0 - 100 % setting range • External manual operation via external signal (0 - 10 V) = Function |2E | Switch over between settings on the device and external manual operation via digital input ( IO Setup: fuction |7D | ). • Measurement value = function |7E | e.g.
Operating Instructions – model series PXDM6A / PXDM10A 9.7 Programming Menu group Start Start Start PIN input PIN input The service menu for the installation can be protected against unintentional changes by a pin code. With further pin codes putting back to pre-setting is possible. PIN 0010 Opening service menu, if PIN-protection activated PIN 1234 Opening “setting”.
Operating Instructions – model series PXDM6A / PXDM10A “Set external1” Programming Signal to “E1” / “GND” “Set external2” Signal to “E2” / “GND” “Set Intern1” Menu “Set Intern1” “Set Intern2” Menu “Set Intern2” Info for mode controller 2.01 ... 6.01 Current actual value measured on the sensor 1. Depending sensor-type in: mbr, m3/s, m/s, Pa, %, bar, m3/h, °C, V, mA, etc. E1 Actual For operation with two sensors display for “2 actual”.
Operating Instructions – model series PXDM6A / PXDM10A 9.9.3 Programming Save user settings restore with PIN 9090 Save User Setup The individually made device configurations (User Settings) can be saved and, with the corresponding PIN input (9091), can be reestablished. By entering PIN 9090 the individually made device configurations can be reestablished Start - PIN Input).
Operating Instructions – model series PXDM6A / PXDM10A 9.9.6 Programming Minimum speed cut off Min. speed cut off This function is primarily significant for installation of the device as a pure P Controller in refrigeration and air-conditioning technology. For operation mode speed controller 1.01 without function! Msco = OFF (factory setting) If no “Min. speed” is adjusted, the fan stops with reaching the desired value. If “Min. speed” is adjusted (e.g.
Operating Instructions – model series PXDM6A / PXDM10A 9.9.8 Programming Reverse action of the control function Val>Set=n+ For the effect of the regulation there are two functions: • ON for “Val > Set = n+” increasing Fanlevel for increasing actual value over Setpoint. • OFF for “Val > Set = n+” increasing Fanlevel for decreasing actual value below Setpoint. For special applications an external switch over of the control function is possible ( IO Setup).
Operating Instructions – model series PXDM6A / PXDM10A Integration time = correction time Setting range: 0 - 200 % smaller = faster bigger = more slowly TI 9.9.10 9.10 Programming Data on the total control deviation The total control deviation is comprised of the sum of the control deviations for performance quantities and work quantities combined and refers to the specified areas. In direct reference to the acquired input and controlled variables, the maximum deviation to the target value is < ± 5 %.
Operating Instructions – model series PXDM6A / PXDM10A Programming A1 Function | 3A | / | 4A | A1 Function “A min.” and “A max.” Analog Out 10 V 10 V A max: 10 – 5V 5V 5V A min: 0 – 5V Funktion Signal 0 50 100 0 -100 % 16.03.2007 v_a1_funktion_amin_amax.vsd 0 10 1 9 2 8 3 7 4 6 5 5 6 4 7 3 8 2 9 1 10 0 0 20 4 2 18 5,6 4 16 7,2 6 14 8,8 8 12 10,4 10 10 12 12 14 16 18 8 6 4 2 13,6 15,2 16,8 18,4 20 0 20 20 -27 -16.8 18,4 16,8 15,2 13,6 -6.6 3.6 13.
Operating Instructions – model series PXDM6A / PXDM10A 10D 9.10.2.2 Programming “Reset” 11D Setting Max. Speed “ON” / “OFF” 12D Motorheating ON / OFF (not for 1~ voltage controller) 13D Reverse direction of rotation “right-hand” / “left-hand” (only for frequency inverter with 3 ~ output) 14D “Freeze function” = maintain momentary modulation value Enable ON/OFF function |1D | Remote ON/OFF (electronic disconnection) and Reset after a motor malfunction via floating contact.
Operating Instructions – model series PXDM6A / PXDM10A Programming Contact e.g. at ditgital input “Digital In 1” (depending on device type at terminals “D1” - “D1”or “D1” “24 V”). For “D1” Inverting “OFF”, limitation active at closed contact. 1 ----- Controller 1 n = 0- 80 % 0 n = 0- 100 % 24V D1 D1 10.05.2007 v_3d_limit.vsd 0 1 1 9.10.2.
Operating Instructions – model series PXDM6A / PXDM10A Programming Operation with “Set Intern2” is signalized by the moon symbol for reduced operation. “Set extern1” under “settings” must be programmed to “OFF”. Frequency Switch over between “Setpoint1” and “Setpoint2” (for modes as controller higher 2.01 ) Contact e.g. at ditgital input “Digital In 1” (depending on device type at terminals “D1” - “D1”or “D1” “24 V”).
Operating Instructions – model series PXDM6A / PXDM10A 9.10.2.8 Programming Automatic control / speed manual, Function |7D | (mode 2.01 ) Switch over between automatic control to set target value (depending on the activation: “Setpoint1”, “Setpoint2”) and the default for “manual operation” set at the device. If for Analog In 2 “E2 function” is programmed to |2E | switch over between “Setpoint1” or “Setpoint2” and external manual operation.
Operating Instructions – model series PXDM6A / PXDM10A 9.10.2.11 Programming Setting Max. Speed ON / OFF function |11D | The value for “Max Speed” adjusted in menu “Settings”, is activated over a digital input. I.e. the unit works independently of the controller function firm with this value. Contact e.g. at ditgital input “Digital In 1” (depending on device type at terminals “D1” - “D1”or “D1” “24 V”). • “D1 Inverting” = “OFF”: “Max. Speed” 1 active at closed contact • “D1 Inverting” = “ON”: “Max.
Operating Instructions – model series PXDM6A / PXDM10A 9.10.3 Programming Inverting analog inputs “E1” / “E2” After programming the signal or sensor type, an inversion of the inputs can be carried out. Factory setting for Inverting inputs = “OFF” (if input activated) (signal: 0 - 10 V, 0 - 20 mA, 4 - 20 mA). For activation using inverted default signals or sensors with inverted output signals proportional to the measurement range, switch inverting to “ON” (Signal: 10 - 0 V, 20 - 0 mA, 20 - 4 mA).
Operating Instructions – model series PXDM6A / PXDM10A Programming 2K Fault indication (factory setting for “K2”, non inverting). Energized for operation without fault, for enable “OFF” not energized. De-energized at line, motor and controller fault, Sensor fault dependent on programming, external fault at digital input.
Operating Instructions – model series PXDM6A / PXDM10A Programming Add-on module type Z-Modul-B Program the additional inputs and outputs likewise in “IO Setup”. After connecting the module, the settings menus are automatically expanded to include the additional inputs and outputs. • 1 x analog input 0 - 10 V. For mode 1.01 without function, starting from 2.01 funktion |1E | or |2E | possible. – Function |1E | for external target value function. – Function |2E | for external manual operation.
Operating Instructions – model series PXDM6A / PXDM10A 9.11 Programming Limits Menu group Limits Limits 9.11.1 Limit indication depending on modulation Following functions can be allocated to the limit indication Level. Function OFF without function 1L Indication with the centralized fault of a programmed relay (IO allocation Function |2K | ). Warning symbol in display, “AL” code in events memory. 2L Is merely displayed in the events menu as message “msg”.
Operating Instructions – model series PXDM6A / PXDM10A 9.11.2 Programming Limit indication depending on setting or sensor signal Following functions can be allocated to the limit indication Lmt E1 Function OFF without function 1L Indication with the centralized fault of a programmed relay (IO allocation Function |2K | ). Warning symbol in display, “AL” code in events memory. 2L Is merely displayed in the events menu as message “msg”.
Operating Instructions – model series PXDM6A / PXDM10A 9.11.3 Programming Limit indication depending on (offset) to Setpoint In operating modes as a controller (via 2.01 ), two limit indicators can be carried out based on the set target value (Setpoint) and measured actual value (on E1).
Operating Instructions – model series PXDM6A / PXDM10A 9.12 Programming Motor Setup Menu group Motor Setup Motor Setup 9.12.1 Adjusting of CosPhi for motor The control device is set to CosPhi = 0.80 at the factory. For optimal control response, the CosPhi of the installed motor must be entered ( specification on the type identification tag of the motor). CosPhi 9.12.2 CosPhi The output voltage of the unit depends on the inductance of the motor (CosPhi).
Operating Instructions – model series PXDM6A / PXDM10A 9.12.3 Programming Suppression of speeds Suppression of up to three speed ranges. Under certain circumstances, it is possible to prevent disturbing noises that can arise at certain speeds due to resonances. Example for suppression of 2 ranges (Idealized principle diagram) A 100 % 2 50 % 35 % max 1 Setting depending on device type in: %, Hz, rpm 15 % min 09.05.2007 v_ausblendung_prz.
Operating Instructions – model series PXDM6A / PXDM10A 10 10.1 Menu tables Menu tables Menues of operating modes Mode 1.01 2.01 2.03 2.04 2.02 2.05 Parameter PIN input 3.01 3.02 3.03 3.04 User Setting 4.01 4.02 4.03 5.01 5.02 6.01 ----- ----- ----- Factory setting ----- ----- ----- Start ----- ----- ----- Language GB GB GB GB GB GB GB GB GB Reset OFF OFF OFF OFF OFF OFF OFF OFF OFF Mode 1.01 2.01 2.03 2.04 2.02 2.05 3.01 3.02 3.03 3.04 4.01 4.02 4.03 5.
Operating Instructions – model series PXDM6A / PXDM10A Mode 4.01 4.02 4.03 5.01 5.02 T-Band SA 4.02 + 4.03 = 30.0 K 5.02 = 30.0 K T-Start SA 4.02 + 4.03 = 15.0 °C 5.02 = 15.0 °C P-Min SA 4.02 + 5.02 = 4.03 = 70.0 m3h 70.0 Pa 1.01 2.01 2.03 2.04 Menu tables 2.02 2.05 Parameter 3.01 3.02 3.03 3.04 User Setting 6.01 Factory setting Min. AnalogOut 2.03 = 0 % Max. AnalogOut 2.03 = 100 % OffsetDigitalOut 2.03 = 1.0 K Hyst.DigitalOut 2.03 = 1.0 K Alarm Minimum 2.03 = 0.
Operating Instructions – model series PXDM6A / PXDM10A Mode 1.01 2.01 2.03 2.04 2.02 3.01 3.02 2.05 Parameter Menu tables 3.03 3.04 User Setting 4.01 4.02 4.03 5.01 5.02 6.01 Factory setting E2 Min. ----- ----- ----- ----- ----- ----4.03 = 35.0 °C ----- ----- E2 Max. ----- ----- ----- ----- ----- ----4.03 = 65.0 °C ----- ----- E2 Decimals ----- ----- ----- ----- ----- ----4.03 = 1 ----- ----- E2 Unit ----- ----- ----- ----- ----- ----4.
Operating Instructions – model series PXDM6A / PXDM10A Mode 1.01 2.01 2.03 2.04 2.02 2.05 Parameter 3.01 3.02 Menu tables 3.03 3.04 User Setting 4.01 4.02 4.03 5.01 5.02 6.01 Factory setting D2 Function OFF OFF OFF OFF OFF OFF OFF 4.03 = 5D OFF OFF D2 Inverting ----- ----- ----- ----- ----- ----- ----4.03 = OFF ----- ----- D2 Busmode ----- ----- ----- ----- ----- ----- ----4.
Operating Instructions – model series PXDM6A / PXDM10A Mode 1.01 2.01 2.03 2.04 2.02 2.05 Parameter 3.01 3.02 Menu tables 3.03 3.04 User Setting 4.01 4.02 4.03 5.01 5.02 6.01 Factory setting Lmt E2 min. ----- ----- ----- ----- ----- ----- ----- ----- ----- Lmt E3 max. ----- ----- ----- ----- ----- ----- ----- ----- ----- Lmt E2 Hyst. ----- ----- ----- ----- ----- ----- ----- ----- ----- Lmt E2 Del.
Operating Instructions – model series PXDM6A / PXDM10A 10.2 Menu tables Possible allocation of the IOs, PINs Analog outputs A / A2 Function Description function A / A2 1A Constant voltage +10 V 2A proportional level control 3A proportional input E1 4A proportional input E2 5A Group control 6A only 2.03 Cooling function (not for Z-Modul-B) 7A only 2.03 Heating function (not for Z-Modul-B) Digital inputs D1..D5 Function OFF Description function D1..
Operating Instructions – model series PXDM6A / PXDM10A Menu tables Digital outputs K1..K4 Function OFF Description function K1, K2 ,K3*, K4* No function Relays remain always de-energized 1K Operating indication (factory setting for “K1”, non inverting). Operation without fault, reports enable “OFF” 2K Fault indication (factory setting for “K2”, non inverting). Energized for operation without fault, for enable “OFF” not energized.
Operating Instructions – model series PXDM6A / PXDM10A 11 Diagnostics menu Diagnostics menu The diagnostics menu supplies information about the momentary operating condition of the device. Diagnostic 00056:46:13 O = Operation, T = Time, C = Controller The time counting runs, as soon as mains voltage is connected (without fault). If events step on (Motor fault, External Error, etc.), the period of operation is stored at Events).
Operating Instructions – model series PXDM6A / PXDM10A Events / Fault signals Status digital input 4 (Digital In 4*) OFF = terminals D4 - GND bridged ↔ ON = terminals D4 - GND not bridged D4 Status digital input 5 (Digital In 5*) OFF = terminals D5 - GND bridged ↔ ON = terminals D5 - GND not bridged D5 OFF = relay K1 de-energized: terminals 11 - 12 bridged ON = relay K1 energized: terminals 11 - 14 bridged K1 OFF = relay K2 de-energized: terminals 21 - 22 bridged ON = relay K2 energized: terminals 21 -
Operating Instructions – model series PXDM6A / PXDM10A Events / Fault signals 2. Alarms with code |AL | Events during which the device automatically restarts operation after the cause of the malfunction has been remedied (e.g. mains failure), or remains in operation (e.g. externally-trunked centralized fault). External error 3. Error with code |Err | Events that lead to a disconnection of the controlled output (e.g. excess motor temperature). Restarting is only possible after a reset (locked).
Operating Instructions – model series PXDM6A / PXDM10A Display Code* LED Code AL Relais switches Cause ** internal Operation Fault - - X Events / Fault signals Reaction of Controller Adjustment fault EEP damaged works with defaults EEP error AL controller runs with the read settings - X X EEP data incorrectly EEP Corruption AL 3 AL - X overload - External error AL - - - - Lmt E1 min AL Lmt E1 max. Sensor 1 Msg or.
Operating Instructions – model series PXDM6A / PXDM10A 13 13.1 Enclosure Enclosure Technical data The information on the rating plate is valid for a maximum ambient temperature of 40 °C. Type Part.-No. Rated current for 40 °C {1} Line fuse max. {2} [A] [A] Integrated semicon- Heat dissipation ductor fuse max. approx. {3} {1} [Part.-No.] Weight [W] [kg] 30 2.25 50 2.75 Line voltage 3 ~ 208...415 V, (-10 %...
Operating Instructions – model series PXDM6A / PXDM10A 13.1.1 Enclosure Performance reduction during elevated ambient temperatures The maximum permissible ambient temperature for the device is 40 °C or 50 °C depending on version. Up to this temperature, loading (maximum continuous current) with the specified rated current is possible.
Operating Instructions – model series PXDM6A / PXDM10A 13.2 Enclosure Connection diagram Ucontrol PXDM6...35(A)(Q) J1 8 Kontaktbelastung Contact rating max. AC 250 V 2 A 7 TB/TP In Digital In 1 TB D1 A1 24V TB D1 GND 24V GND N L1 L2 L3 U V 11 W 14 12 21 K1 24 22 Analog Out 1 24 V DC Out Analog In 2 TF In 1/2 Digital In 2 E1 E2 T D2 GND GND T D2 Analog In 1 1 + Ausgang Output 0...
Operating Instructions – model series PXDM6A / PXDM10A 13.2.1 • Enclosure Connection suggestion for several motors with motor protection unit type STDT Full motor protection by switch-off when activating the attached thermostat switches “TB”. Reset after malfunction by key press. Line protection: A thermal over current sensor and a magnetic short circuit releasing elements are the parts of the integral line protection. Adjustment to the thermal overcurrent sensor to the max.
Operating Instructions – model series PXDM6A / PXDM10A 13.
Operating Instructions – model series PXDM6A / PXDM10A 13.5 Index Manufacturer reference Our products are manufactured in accordance with the relevant international regulations. If you have any questions concerning the use of our products or plan special uses, please contact: Systemair Industrievägen 3 73930 Skinnskatteberg Telefon:+46 (0) 222 440 00 Telefax:+46 (0) 222 440 99 mailbox@systemair.se www.systemair.se L-BAL-E180-GB 1243 Index 001 Part.-No.