MA FRICO SIRE ADVANCED FUNCTIONS AC GB 160927

SIRe Advanced Air Curtains
12
Installer menu>Heating
settings>Return water temp.
Return temp. sensor
Not connected
Installer menu>Heating
settings>Return water temp.
Return temp. sensor
Return temp. limit
Stepless heat control
Sensor calibration
Return water temp.
>Installer menu>Heating
settings
Connected
Installer menu>Heating
settings>Return water temp.
Return temp. limit
OFF
Installer menu>Heating
settings>Return water temp.
Return temp. sensor
Return temp. limit
>Installer menu>Heating
settings
Stepless heat control
ON
>Installer menu>Heating
settings
Control range limit
Return water temp.
Stepless heat control
>Installer menu>Heating
settings
3
>Installer menu>Heating
settings
Control range limit
Sensor calibration
Control range limit
Stepless heat control
Stepless heat control
>Installer menu>Heating
settings
35°C
>Installer menu>Heating
settings
Stepless heat control
Sensor calibration
Control range limit
>Installer menu>Heating
settings
Stepless heat control
Heating step limit
Sensor calibration
>Installer menu>Heating
settings>Sensor calibration
Room temp. sensor
>Installer menu>Heating
settings>Sensor calibration
Room temp. sensor
Outdoor temp. sensor
0.0 K
GB
Factory setting
Room temperature sensor: 0.0K (-10K – 10K)
Outdoor temperature sensor: 0.0K (-10K –
10K)
Stepless heat control
Unit with electrical heating
For stepless control of electrical heating, for
example via external triac.
Unit with water heating
To use Advanced fully, stepless heat control
must be used.
Return water temp.
Unit with water heating
If there is a demand for the temperature
of the return water not to exceed a certain
value, this function is activated under Return
water temp. A return water temperature
sensor (proximity sensor SIReWTA, option)
must then be installed on the return water
pipe.
Install Return temp. Sensor to Connected
and select max return temperature (15-90 °C)
using the turn wheel. During operation, this
function limits the valve’s degree of opening,
which reduces the flow and the return tempe-
rature.
Factory setting
Return temp. sensor: Not connected
(Connected)
Return temp. limit: Off (15 – 90°C)
Control range limit
The maximum room temperature that a user
can select is limited to between 5 – 35°C.
Factory setting
Control range limit temperature: 35°C (5 –
35°C)
Sensor calibration
If the sensor displays the wrong values these
can be calibrated. Some display errors may
occur, but this is primarily due to the location
(cold/hot surfaces etc). The value + or – adds
to or subtracts from the measured value
(for example +2K gives an increase of the
displayed value of 2 degrees).
Stepless heat control: ON (Off - not
selectable)