Original instructions SIRe Basic Air Curtains Water With quick guide SIReB C For wiring diagram, please see last pages
GB SIRe Basic Air Curtains Water Quick guide/start up Enter ID/Operation without control unit Check that all constituent parts are present (see section Constituent parts). The control system can control one or more units in parallel (max 9). Each unit must get a unique ID number (1-9) which is set in the ID selector of the PC board. E.g. Unit 1: ID=1, unit 2: ID=3 If the external control for some reason has not been installed the unit can still be run temporarily.
SIRe Basic Air Curtains Water GB Start up System supplied with power. Three digits 1.4.0. (software version) is quickly shown in th the status window followed by three horizontal lines. After about 30 seconds the prevailing room temperature is then shown in the status window. Use arrow up/down and set the desired room temperature, fan speed step and heating step. To change a setting push the round button (confirm), the setting will start to flash and can be adjusted by using the arrow up/down.
GB SIRe Basic Air Curtains Water Contents Quick guide/start up Advice about location Connect the system Wiring diagrams Enter ID/Operation without control unit Start up 12 12 12 12 13 Constituent parts SIReB 15 Option 16 16 Max.
GB SIRe Basic Air Curtains Water Constituent parts SIReB Integrated in the air curtain C PE N L SUPPLY 230V X5 C2 SIReUB1, control unit Basic Wall unit cover X4 C1 X3 ROOM ACTUATOR 230V SIReB1, integrated PC Board Base SIReIT, internal temperature sensor SIReCC, modular cable Dimensions constituent parts Typ Description SIReUB1 SIReB1 SIRelT SIReCC605 Controll unit Integrated PC board Base Internal temperature sensor Modular cable RJ12 (6/6) HxWxD [mm] 120x70x35 L [m] 1 5 15
GB SIRe Basic Air Curtains Water Option SIReRTX, external room temperature sensor SIReCJ4, joint piece SIReCJ6, joint piece SIReCC, modular cable Type Description HxWxD SIReRTX SIReCJ4 SIReCJ6 SIReCC603 SIReCC605 SIReCC610 SIReCC615 SIReCC403 SIReCC405 SIReCC410 SIReCC415 External room temperature sensor Joint piece for two pcs. RJ11 (4/4) Joint piece for two pcs.
GB SIRe Basic Air Curtains Water Water control - valve kit SD230 VOS TBVC BPV10 AV Water control - option SD230 VOSP TBVCMP BPV10 AV VAT, adjustment tool for valve package. Type RSK-no.
GB SIRe Basic Air Curtains Water Operating modes Set values Use arrow up /down to choose desired room temperature, fan speed step and heating step. Operating modes Factory settings gives manual control of fan and heating controlled by thermostat on/off. Auto mode Change parameter P04 from 0 to 1 (see list of parameters on next page) to active auto mode. Thermostat controls both fan and heating Push the confirm button and the digit(s) starts to flash.
GB SIRe Basic Air Curtains Water Control unit SIReUB1 Overview Prevailing room temperature C 2 0. 8 Statuswindow Arrow up Scroll up Confirm C Arrow down Scroll down Desired room temperature 20 Fan speed step Alarm Red led Run signal Green led ON/OFF button - 3 Heating step _ 1 Explanations Status window The status window has four main displays: prevailing and desired room temperature, fan and heating setps. Alarm codes and parameter settings can also be shown in the status window.
GB SIRe Basic Air Curtains Water Installer menu Parameter menu Keep Confirm button pressed until P00 is shown in the status window. Use arrow up / down to scroll between the parameters. Press Confirm button once to change a setting in the parameter menu. Flashing values can be adjusted using the arrow up/down and then confirm. Keep the Confirm button pressed to return to the status window. (Returning automatically to the status window after about 50 seconds). P.P0. 0.01 PPP..0.00222 P 0P.
GB SIRe Basic Air Curtains Water Alarm and error codes Reset alarm Overheat protection Note! Before resetting, check that the fault is rectified and there is nothing to prevent the unit from being recommissioned! When the fault is rectifed, the alarm is reset according to description below. If "wrong" button is pressed the alarm display disappears but returns in status window after about 20 seconds. At the first start up alarm and error codes can occur, these can usually be reset without action.
GB SIRe Basic Air Curtains Water Table - Alarm Alarm Cause Action Thermal switch has deployed. One or several motors have overheated. (Only units with withdrawn thermal switches.) Check that nothing is obstructing the unit’s air intake and exhaust. When the overheated motor has cooled the thermal switch shuts again and the alarm can be reset. At repeated alarms, check the motors, replace damaged motors.
Internal PC Board Base 44 X5 C2 SIReB1 Wiring diagram - Basic X4 C1 X3 ROOM PE N L SUPPLY 230V ACTUATOR 230V SIReSD230 SIReRTX (optional) C SIReUB1 SIRe Basic Air Curtains Water
External PC Board Base C1 X4 SIReB1X C2 Pot.
SIRe Basic Air Curtains Water Wiring diagram - Basic SIReB1 SIReSD230 X5 C2 X4 C1 X3 ROOM PE N L SUPPLY 230V ACTUATOR 230V SIReB1 SIReSD230 X5 C2 X4 C1 X3 ROOM PE N L SUPPLY 230V ACTUATOR 230V SIReB1 SIReSD230 X5 C2 46 X4 C1 X3 ROOM PE N L SUPPLY 230V ACTUATOR 230V SIReRTX (optional) SIReUB1