MANUAL SIRE BASIC AC ELECTRIC

Installer menu
Parameter menu
Keep Confirm button pressed until P00 is
shown in the status window. Use arrow up /
down to scroll between the parameters. Press
Confirm button once to change a setting in
the parameter menu. Flashing values can be
adjusted using the arrow up/down and then
confirm. Keep the Confirm button pressed
to return to the status window. (Returning
automatically to the status window after
about50seconds).
Parameter description
P.00 Temperature difference heating steps
Sets the difference between the heating steps.
Factory setting of 1,0 and a desired room
temperatureof20°Cgivesthefollowing
operation:Low heating step is connected
at+19,5°C(disconnectedat+20,0°C).
If temperature continue to drop below
+18,5°Canotherheatingstepisconnected
(disconnectedat+19,0°C),etc.
P.01 Overheating alarm ON/OFF
Possibility to block the alarm (only valdid for
units with internal temperature sensor).
P.02 Over run time
Time when the fan continue to run when the
heat has been activated (only valid for units
with internal temperature sensor).
P.03 Temperature limit for over run
Over run time is cancelled if the internal
temperature drops below this set value (only
valid for units with internal temperature
sensor).
P.04 Fan control
Choose manul (0) or auto (1) mode, read
more under section Operating mode.
P.05 Internal temperature
Prevailing internal temperature. Only the
peak value is shown when several units are
connected (only valid for units with internal
temperature sensor).
P.06 - P.13 Run time
Run time for fan and heating steps.
SIRe Basic Air Curtains Electric
18
GB
P13
.
P02
.
P02
.
P02
.
P02
.
P02
.
P02
.
P01
.
P00
.
List of parameters
Parameter-
number
Description Setting
range
Factory
setting
P. 0 0 Temperature difference between heating steps 0,5-10 1.0 °C
P. 0 1 Overheting alarm ON/OFF ON=1; OFF=0 1/0 1
P.02 Over run time when heat has been activated 10-300 180 seconds
P.03 Temperature limit for fan over run 10-40 30 °C
P.04 Fan control: Menul rorAuto; 0=Menul, 1 = Auto 0/1 0
P.05 Display of unit internal/outlet temperature 0-100
P.06 Run time fan step 1 0-99999
P.07 Run time fan step 2 0-99999
P.08 Run time fan step 3 0-99999
P.09 Run time fan step 4 0-99999
P. 1 0 Run time fan step 5 0-99999
P. 11 Run time heating step 1 0-99999
P. 1 2 Run time heating step 2 0-99999
P. 1 3 Run time heating step 1+2 0-99999