Configuration Manual
Version Document ID 
A
001   Access 4x Configuration manual 
   44 (56)  2018-07-11 
Note!  If the sensor/signal is not in the list, please activate and configure the 
function and go back in this list to set up a physical position of I/O's 
Analouge inputs  Device  Signal 
e.g Minitoring supply air fan  Controller  DI1 
Avalible digital inputs 
  Monitoring supply air fan 
  Monitoring extract air fan 
  Extended operation low speed 
  Extended operation normal speed 
  Extended operation high speed 
 Fire alarm 
  Smoke sensor alarm 
 External alarm 
  Fire damper position switch 
 Feedback sequence-A 
 Feedback sequence-B 
 Feedback sequence-C 
 Feedback sequence-D 
 Feedback sequence-E 
 Feedback sequence-F 
 Feedback sequence-G 
 Feedback sequence-H 
 Feedback sequence-I 
 Feedback sequence-J 
  Overheated electric heater 
 External stop 
 Alarm acknowledgement 
 Flow switch 
 Defrost switch 
  Rotary exchanger alarm 
  Frost protection switch 
 Recirculation operation 
  Cooling/(heating) changeover 1 
  Cooling/(Heating) changeover 2 
  Filter guard supply air 
  Filter guard extract air 
  Alarm extra fan motor 1 
  Alarm extra fan motor 2 
  Indication extra fan motor 1 
  Indication extra fan motor 2 
  Extra alarm 1 
  Extra alarm 2 
  Extra alarm 3 
  Extra alarm 4 
  Extra alarm 5 
  Extra alarm 6 
  Extra alarm 7 
  Extra alarm 8 
  Extra alarm 9 
  Extra alarm 10 
  Lock PID controller supply 
 Summer/(winter) mode
Device 
Select controller or some off the other device  
Note!  If you not finde your device, se 25.2 to configure/activate your device 
Signal 
Selecta I/O for signal on selected device. 
Note!  It’s possible to select an already used I/O position. 
Please select the same ouputs as wiring diagram describe. 
Or select a free I/O’s position. 
22.3 Analogue outputs 
Configure:  Configuration > I/O allocation 
Analogue outputs shows only actuator/signals as are activade by 
configuration 
Note!  If the sensor/signal is not in the list, please activate and configure the 
function and go back in this list to set up a physical position of I/O’s 
Analouge inputs  Device  Signal 
e.g Heating  Controller  AO1 
Avalible analogue outputs 
 Heating 
 Exchanger 
 Cooling 
 Recirculation 1 
 Recirculation 2 
 Fan heating/cooling 
 Heating 2 
 Cooling 2 
 Exchanger extract 
  External heating/cooling capacity 
 Changeover 1 
 Changeover 2 
  Supply air fan 
  Extract air fan 
 Humidity 
  Step controller 1 
  Step controller 2 
 Extra controller 
 Temperature output 
Device 
Select controller or some off the other device as are active and configure under 
Configuration > System settings > Device List 