Configuration Manual
Version Document 
A
001 
A
ccess V4.X Configuration manual 
   38 (56)  2018-07-11 
followed at a pressure drop alarm. These are found under “Alarm configuration”. 
FS = X1:0 m
3
/h, Y1:10 Pa : X2:2000 m
3
/h, Y2:150 Pa. 
If a constant pressure drop alarm level is wanted, Y1 and Y2 should be set to the 
same value. 
  Extended operation 
Activate:  Configuration > function Configuration > Function Activation 
 No 
 Yes 
Configure:  Configuration > function Configuration > Extended operation 
Extended operation low 
 No 
 Yes 
Extended operation normal 
 No 
 Yes 
Extended operation high 
 No 
 Yes 
Operation settings:  Data & settings > Operation overview > Control overview 
Extended operation 
Actual level of digital inputs for Extended operation. 
Extended operation conditions in priority 
1.  Extended operation high 
2. Extended operation normal 
3.  Extended operation high 
Extended operation time 
 0,30,60.. 
The unit will run for the set time. If the running time is set to 0 the unit will only run 
as long as the digital input is closed. 
The time are “off delay time” 
Extended operation time left 
Run time left to end the extended operation 
  Pretreatment 
Activate:  Configuration > Function Configuration > Function Activation 
 No 
 Yes 