Configuration Manual
Version Document ID 
A
001   Access 4x Configuration manual 
   50 (56)  2018-07-11 
Function 
Configure:  Configuration > System Settings > Device List > Device (n) > Functin > 
…. 
Model  Fan 
(Modbus) 
Rotary 
exchanger 
(Modbus) *1 
Pressure 
transmitter 
Damper 
(Modbus) 
Expansion unit 
(EXOline) 
Function  Supply air fan  Heating *1  Exp1  Heating *1  Exp1 
Exhaust air fan  Exchanger*1  Exp2 Exchanger*1 Exp2 
  Cooling *1  Exp3  Coolingc *1  Exp3 
  Recirculation 1 *1  Exp4  Recirculation 1 *1  Exp4 
  Recirculation 2 *1  Exp5  Recirculation 2 *1  Exp5 
 Fan heating/cooling 
*1 
Exp6 Fan heating/cooling 
*1 
Exp6 
  Heating 2 *1  Exp7  Heating 2 *1  Exp7 
  Cooling 2 *1  Exp8  Cooling 2 *1  Exp8 
 Exchanger extract *1 Exp9 Exchanger extract *1  Exp9 
 Extra heating/cooling 
capacity *1 
Exp10 Extra heating/cooling 
capacity *1 
Exp10 
 Recirculation air  
 Outdoor air  
 Exhaust air  
*1 Only active sequence are selecteble 
Name 
Configure:  Configuration > System Settings > Device List > Device (n) > Name 
 Device (n) 
Select a unique device name. 
This name will be used in Device “drop down list” when you select Device 
under I/O allocation. 
25.3 Preference unit settings 
Configure:  Configuration > System Settings 
Temperature unit 
 Celsius 
 Fahrenheit 
Flow unit 
 m³/h 
 CFM 
 m³/s 
 l/s 
Pressure unit 
 Pa 
 In.wg(x100) 