Configuration Manual
Version Document 
A
001 
A
ccess V4.X Configuration manual 
   19 (56)  2018-07-11 
Defrosting 1 
Defrosting is activated either when the digital signal ”Defrosting” is activated or 
when the value of the analogue input ”Defrosting temperature” falls below the 
defrosting limit (-3°C), or when the analogue signal ”Exchanger extract air 
pressure sensor” rises above the set value for the current pressure. It is 
deactivated when the digital signal is reset, or alternatively when the analogue 
signal exceeds/falls below the limit value plus a settable differential. 
When defrosting: 
A PID-controller compares the defrosting setpoint with the signal ”Defrotsing 
exchanger”. The smallest of the output signal from this controller and the output 
from the ordinary controller is used as output to the dampers. 
Defrosting 2 
Defrosting is activated by measuring the pressure difference over the exchangers 
extract/exhaust side. The differential pressure transmitter is auto calibrated by the 
system to obtain the correct pressure in relation to the airflow. 
Manual calibration is possible, e. g. after cleaning of exchanger. Defrosting is 
possible with by-pass or stop defrosting, adjustable in the display. 
Defrosting is stopped when the desired, adjustable decrease in pressure over the 
heat exchanger is obtained. 
If the decrease of pressure does not happens during defrost cycle, the air handling 
unit is stopped and an alarm is shown in the display. 
Liquid exchanger 
Control 
A mixing valve in the exchanger circulation system is controlled by the analogue signal 
”Exchanger” and digital output (“Sequence-A pump”) for pump control and/or signal 
(“Sequence-A start”) for start heating. 
Defrosting 1 
Deicing is activated either when the digital input sensor ”Defrosting temperature” is 
activated, when the value falls below the deicing limit (-3°C). It is deactivated when the 
digital input is reset or the analogue input rises above the limit value plus a settable 
differential. 
On deicing: 
A PI-controller compares the deicing setpoint with the signal ”Defrotsing Exchanger”. The 
lesser of the output signal from this controller and the output from the ordinary controller is 
used as output to the actuator. 
Pump indication 
A feedback from pump (“Pump sequence-B”) can be used, running indication or 
alarm indication (“Feedback sequence-B”). 