Configuration Manual
Version Document 
A
001 
A
ccess V4.X Configuration manual 
   15 (56)  2018-07-11 
Sequence  Heating  Cooling  Start 
Heating 
Start 
Cooling 
Sequence name 
Sequence-A  3 2  Off 0% 0% Heating 
Sequence-B 1 1 0% 0% Exchanger 
Sequence-C Off 2 0% 0% Cooling 
Sequence-D Off Off 0% 0% Recirculation 1 
Sequence-E Off Off 0% 0% Recirculation 2 
Sequence-F Off Off 0% 0% Fan heating/cooling 
Sequence-G  2 Off  Off 0% 0% Heating 2 
Sequence-H Off Off 0% 0% Cooling 2 
Sequence-I Off Off 0% 0% Exchanger extract 
Sequence-J  Off  Off  0%  0%  Extra heating/cooling capacity 
Configure:  Configuration > Function Configuration > Function Activation> Sequence Configure 
type > Heating (Heating 2) 
Heating type: 
 Water 
 Electric 
 Combi battery 
 Condenser (DX) 
Water heating 
Control 
When the unit is in running mode the heating valve is controlled by the analogue 
output and digital output (“Sequence-A pump”) for pump control and/or signal 
(“Sequence-A start”) for start heating. 
Pump indication 
A feedback from pump (“Feedback sequence-A”) can be used, “running indication 
or alarm indication. 
Frost protection temperature sensor 
The heater return water temperature is measured using the analogue input (”Frost 
protection sensor”). Low temperatures will generate an internal, proportional signal 
that is used to force the heating valve open thereby preventing freeze-up of the 
heater. 
The internal signal will begin to rise as the frost protection temperature falls below 
“Alarm limitation running mode” + “P-band running mode” in order to reach 100 % 
output when the signal has fallen to “Alarm limitation running mode”. 
Frost guard 
When ”Internal signal” reaches 100 % or the digital input (”Defrost switch”) is 
activated, the unit is shut down, the heating output is set to completely open mode 
and an alarm is activated. The unit is restarted when the alarm has been 
acknowledged and the temperature for the frost protection sensor has risen above 
“Alarm limit frost” + “P-Band”. 
The frost protection alarm limits is set in the Data & settings > Temperature control 
> Heating and/or Heating 2. 