Configuration Manual
Version Document 
A
001 
A
ccess V4.X Configuration manual 
   13 (56)  2018-07-11 
Flow transmitter 
DESCRIPTION
 
∗ 
,5
,
 
Flow transmitter supply air 
 K-factor 
 X-factor Default 0,5 
Flow transmitter extract air 
 K-factor 
 X-factor Default 0,5 
Exchanger supply air pressure sensor 
 K-factor 
 X-factor Default 0.96…0.98 
Operation settings:  Data & Settings > Fan control 
  Sequence Configure types 
Activate/configure:  Configuration > Function Configuration > Function Activation 
10 different sequence 
Sequence  Heating  Cooling  Start 
Heating 
Start 
Cooling 
Sequence name 
Sequence-A 2 Off 0% 0% Heating 
Sequence-B 1 1 0% 0% Exchanger 
Sequence-C Off 2 0% 0% Cooling 
Sequence-D Off Off 0% 0% Recirculation 1 
Sequence-E Off Off 0% 0% Recirculation 2 
Sequence-F Off Off 0% 0% Fan heating/cooling 
Sequence-G Off Off 0% 0% Heating 2 
Sequence-H Off Off 0% 0% Cooling 2 
Sequence-I Off Off 0% 0% Exchanger extract 
Sequence-J Off Off 0% 0% Extra heating/cooling capacity 
Menu function  Value  Comments 
Step controller 1   > (Sub menu for step controller 1 settings)  Visible only if Heater electric 
and/or cooler DX are configure 
Step controller 2   > (Sub menu for step controller 2 settings)  Visible only if Heater electric 
and/or cooler DX are configure 
Heating sequence step to start at 100% 
when normal start 
Step 1   
Full heating when outdoor temperature is 
below 
3 °C   
Heating sequence step to start at 100% 
when heating start 
Step 2   
Description on heating sequence ('B' column 'Heating') and cooling sequence ('C' 
column 'Cooling'). See example below. 
Start Heating and Start cooling ('D' column 'Start Heating' and 'E' column 'Start 
Cooling') it starts before (-x%) or after (+x%) of the control signal. 