4.7.4 Operating settings
Adjust CO2 limits for the Fan start/stop function and adjust the minimum run time for CO2 control in the Data & Set-
tings > Demand control > CO2 menu.
Overview:
Data & Settings > Demand control > CO2
04 Apr 13:54
Start limit fan start/stop
800 ppm
Stop hysteresis fan start/stop
160 ppm
Min time for CO2 control 20 min
Step by step:
Note:
Setpoint CO2 not active for this configuration. Setpoint CO2 is only used by CO2 function Mixing damper.
1.
Select Data & Settings from the navigation icons
2. Select Demand control
3. Select CO2
4. Set Start limit fan start/stop to the desired CO2 level to start the fan start/stop function
5. Set Stop hysteresis fan start/stop to the desired amount that the CO2 level needs to decrease to end the
fan start/stop function.
4.8 Fire/Smoke function (Fire)
4.8.1 Activation
Activate the Fire function by selecting the Fire option for Fire/Smoke in the list of available functions in the Configu-
ration > Functions > Function activation menu.
Overview:
Configuration > Functions > Function activation
04 Apr 13:54
Fire/Smoke Fire
Step by step:
1.
Select Configuration from the navigation icons
2. Select Functions
3. Select Function activation
4. Select Fire as Fire/Smoke
157618 | A002