Configuration Manual
Version Document 
A
001 
A
ccess V4.X Configuration manual 
   17 (56)  2018-07-11 
Block step signal if alam 
 No 
 Yes 
Operation settings:  Data & Settings > Temperature control > Heating (Heating 2) 
Sequential control 
Each output step has individually settable on and off values in percent of the 
control signal. The number of steps is equal to the number of heater/chiller groups. 
Minimum on and off times can be set, i.e. the minimum time the step has to be 
inactive or active for a change to occur. 
Binary control 
The heater power outputs should be binary weighted (1:2:4:8 for heating). The 
number of loads to be controlled is set. Thereafter the program will automatically 
calculate the individual Activate levels. Switching differential and minimum on/off 
times can be set. The number of heating steps will be: 2no. of groups-1. In binary 
mode, the analogue output signal may be used to fill out between the steps. The 
signal will go 0…100 % between the Activate of each step. The load connected to 
the analogue signal should have the same size as the smallest of the binary 
groups. In the example below there are 4 heater groups (1:1:2:4) and the total 
number of heating steps is eight. 
As alternative or complement to the above mentioned analogue control, heating 
and cooling can be activated in steps. The internal signal is then used to activate 
digital outputs for control of the heaters/chillers. Up to four heater outputs and 
three cooler outputs can be configured. There are two possible modes: 
3.2 Exchangers 
Activate:  Configuration > Function Configuration > Function Activation> Sequence Configure 
type 
Example 
Order heating sequence: 
1. ”Exchanger” 
2. ”Exchanger extract” 
Y1
=
1
1 
2
1 
4
1 
2
1 