Configuration Manual
Version Document 
A
001 
A
ccess V4.X Configuration manual 
   20 (56)  2018-07-11 
3.3 Cooler 
Activate:  Configuration > Function Configuration > Function Activation> Sequence Configure 
type 
Activate extra cooler coil 
Example:  Order cooling sequence: 
1. ”Exchanger” 
2. ”Cooler” 
3. ”Cooler 2” 
Sequence  Heating  Cooling  Start 
Heating 
Start 
Cooling 
Sequence name 
Sequence-A 2 Off 0% 0% Heating 
Sequence-B 1 1 0% 0% Exchanger 
Sequence-C Off 2 0% 0% Cooling 
Sequence-D Off Off 0% 0% Recirculation 1 
Sequence-E Off Off 0% 0% Recirculation 2 
Sequence-F Off Off 0% 0% Fan heating/cooling 
Sequence-G Off Off 0% 0% Heating 2 
Sequence-H Off 3 Off  0% 0% Cooling 2 
Sequence-I Off Off 0% 0% Exchanger extract 
Sequence-J  Off  Off  0%  0%  Extra heating/cooling capacity 
Example:  Order cooling sequence: 
1. ”Exchanger” 
2. ”Cooler 2” 
3. ”Cooler” 
Sequence  Heating  Cooling  Start 
Heating 
Start 
Cooling 
Sequence name 
Sequence-A 2 Off 0% 0% Heating 
Sequence-B 1 1 0% 0% Exchanger 
Sequence-C Off 3 2  0% 0% Cooling 
Sequence-D Off Off 0% 0% Recirculation 1 
Sequence-E Off Off 0% 0% Recirculation 2 
Sequence-F Off Off 0% 0% Fan heating/cooling 
Sequence-G Off Off 0% 0% Heating 2 
Sequence-H Off 2 Off  0% 0% Cooling 2 
Sequence-I Off Off 0% 0% Exchanger extract 
Sequence-J  Off  Off  0%  0%  Extra heating/cooling capacity 
Configure:  Configuration > Function Configuration > Function Activation> Sequence Configure 
type > Cooling (Cooling 2) 
Cooling type: 
 Water 