Configuration Manual
Version Document 
A
001 
A
ccess V4.X Configuration manual 
   14 (56)  2018-07-11 
Adjustable range -100…100%. 
Example:  Start Cooling 
If you want Cooling (Sequence-C / configured as DX) to start earlier than the PID 
loop, then set -10% in "Start cool" then will DX cooling start when Exchanger 
signal is 90% (PID loop signal for exchanger, if "cool recovery" = active). 
Sequence  Heating  Cooling  Start 
Heating 
Start 
Cooling 
Sequence name 
Sequence-A 2 Off  0%  0%  Heating 
Sequence-B  1  1  0% 0% Exchanger 
Sequence-C  Off  2  0%  -10% 0%  Cooling 
Sequence-D  Off  Off  0%  0%  Recirculation 1 
Sequence-E  Off  Off  0%  0%  Recirculation 2 
Sequence-F  Off  Off  0%  0%  Fan heating/cooling 
Sequence-G Off Off  0%  0%  Heating 2 
Sequence-H  Off  Off  0%  0%  Cooling 2 
Sequence-I  Off  Off  0%  0%  Exchanger extract 
Sequence-J  Off  Off  0%  0%  Extra heating/cooling capacity 
3.1 Heating 
Activate:  Configuration > Function Configuration > Function Activation> Sequence Configure 
type 
Example:  Order heating sequence: 
1. ”Exchanger” 
2. ”Heating” 
3. ”Heating 2” 
Sequence  Heating  Cooling  Start 
Heating 
Start 
Cooling 
Sequence name 
Sequence-A 2 Off  0%  0%  Heating 
Sequence-B  1  1  0%  0%  Exchanger 
Sequence-C  Off  2  0%  0%  Cooling 
Sequence-D  Off  Off  0%  0%  Recirculation 1 
Sequence-E  Off  Off  0%  0%  Recirculation 2 
Sequence-F  Off  Off  0%  0%  Fan heating/cooling 
Sequence-G  3 Off  Off  0%  0%  Heating 2 
Sequence-H  Off  Off  0%  0%  Cooling 2 
Sequence-I  Off  Off  0%  0%  Exchanger extract 
Sequence-J  Off  Off  0%  0%  Extra heating/cooling capacity 
 :  Order heating sequence: 
1. ”Exchanger” 
2. ”Heating 2” 
3. ”Heating” 