Communication Manual
Table Of Contents
  Chapter 2 │System integration  8 
BACnet 
Access  from  software  version  4.0-1-05  is  capable  of  communication  via  the  BACnet-ASC 
(Application  Specific  Controller)  protocol  and  from  4.3-1-00  with  BACnet  AAC  (Advanced 
Application Controller). 
In order to connect a Access application to a BMS (Building Management System) via BACnet/IP 
use the TCP/IP port. 
BACnet/IP configuration (Activation status of BACnet/IP protocol) 
Upon delivery, the BACnet/IP protocol is disabled as a default. To enable BACnet communication, 
simply change the setting “No” to “Yes”. 
BACnet device name 
This is the devices name that is shown on the BMS when a device is discovered. 
BACnet device ID 
The ID of a device, used to identify it on the BACnet network. This number cannot be duplicated 
anywhere on the BACnet network and must therefore be unique. 
BBMD address and BACnet/IP port number 
The BBMD address (BACnet/IP Broadcast Management Device) is used for discovering devices that 
are attached to different BACnet/IP subnets and separated by an IP router. The address is entered as 
host:port, where “host” can be the host’s name if DNS is configured. If DNS is not configured, the 
host address should be entered in the format “xxx.xxx.xxx.xxx”, followed by the port number (default 
setting 47808). 
Example: mybbmd:47808 (with DNS configured) or 10.100.50.99:47808 
Note! When BBMD address is configured in Access, will make the Access controller to a BACnet/IP 
Foreign Device, which then means that the Access will not answer any UDP broadcast in the net other 
than from that particular BBMD. When assigning BBMD, some BBMD vendors mentions that not 
only the Device ID must be unique but also the Device Name within the BACnet network. For further 
information, please consult the specific BBMD vendors and/or BACnet routers literature.










