Configuration Manual
Version Document 
A
001 
A
ccess V4.X Configuration manual 
   40 (56)  2018-07-11 
The extra controller can also be used for humidity control. The cooling battery will 
be used for dehumidification if the room/extract air humidity is too high. The 
function uses the sensor “Extra unit temp” and is placed immediately after the 
cooling battery. The function also requires use of a room humidity or extract air 
humidity sensor. 
Example: 
If the room humidity exceeds the setpoint for the function, the cooling battery will 
be controlled by the external controller. The heater is controlled normally. When 
the room humidity falls below the setpoint once more, the cooling control will return 
to normal control. A hysteresis of 1 % is added to the function. 
The function can be used for “Cascaded room temperature control”, “Cascade 
connected extract air temperature control”, “Outdoor compensated room 
temperature control” as well as “Outdoor compensated extract air control”. 
An alarm will be triggered if “Extra controller” is in manual position or if a sensor 
error occurs. 
Operation settings:  Data & settings > Temperature control > Supply air controller 
Setpoint extra controller 
 18 °C 
Temperature extra controller 
  Actual value for Extra temperature controller 
  External switch (External stop) 
Activate:  Configuration > Function Configuration > Function Activation 
 No 
 Yes 
The signal “External stop” will stop the unit, even if the time channel or one of the 
signals “Extended Operation, Low, “Extended Operation, Normal” or “Extended 
Operation High” says it should stay in running mode. 
  External motor control 
Activate:  Configuration > Function Configuration > Function Activation 
 No 
  One fan control 
  Two fan control 
Extra fan motor control 
Configure:  Configuration > Function Configuration > Extra fan motor control 
Motor control 1 
 None 
 Motor protection 
 Run indication 
Mode motor control 1 
  Only Digital input 
  Normal time channel 