Configuration Manual
Version Document 
A
001 
A
ccess V4.X Configuration manual 
   10 (56)  2018-07-11 
Settings Frost protection (1/2/3) 
Settings for stopped and running mode 
Settings Exchanger & defrosting 
Step control settings for Step start/stop points, min switch time, outdoor temp/fan 
speed block of steps etc.) 
Step settings 
Fan heat/cool settings (Fan compensation) 
Pretreatment 
  Fan control 
Activate:  Configuration > Function Configuration > Function Activation 
Fan control type 
1. Pressure 
2. Flow 
3. Manual 
4. External 
5.  Supply air pressure and extract air slave 
6.  Supply air pressure and extract air flow slave 
7.  Extract air pressure and supply air slave 
8.  Extract air pressure and supply air flow slave 
The rotational speed is controlled by output signal (0 – 100%). 
A digital Activate signal is normally used for each fan (“Supply air fan start” and 
“Extract air fan start”), for sending a start signal to the frequency converters/EC-
motor. The start signal is activated as long as the fan is expected to be running. 
For the supply and extract air fans, there are 1..3 individually settable setpoint 
values, one corresponding to Low speed, one corresponding to normal speed and 
one corresponding to high speed. Changing between the setpoint values is done 
using the timer channels for normal low and high speed or using digital input 
signals. Extended Operation, Low, normal and high speed, see chap.14. 
Pressure 
During pressure control, two separate analogue output signals are used for supply 
and extract air and two separate analogue input signals for supply and extract air 
for pressure transmitters. The fan speeds are controlled via frequency converters, 
thereby maintaining constant pressure. The pressure transmitter inputs are 
scalable using “Volt minimum/Minimum (pressure)” and “Volt maximum/Maximum 
(pressure)”. 
Flow 
Instead of giving a pressure setpoint value, it is possible to use an airflow volume 
value. The value from the pressure transmitter is recalculated to a volume flow 
using the formula below and the fans will be controlled to give a constant flow. 
Flow = K *∆ P
X
Where K and X are settable constants dependent on the fan size and ∆ P is the 
differential pressure, measured over the fan. Each fan has its own set of 
parameters. 
X is normally 0.5 indicating that the flow is proportional to the square root of the 
differential pressure. 
Flow presentation can be selected, when fan control type not are “Flow”. 