| Quick configuration guides
4.4.3 Allocation
Select I/O (in-/output) placement for where the room temperature sensors are connected to the controller in the Con-
figuration > I/O allocation settings > Analog inputs menu.
Overview:
Configuration > I/O allocation settings > Analog
inputs
04 Apr 13:54
Analog inputs
Device Position
Room temperature 1
Controller Select I/O
Room temperature 2
Controller Select I/O
Room temperature 3
Controller Select I/O
Room temperature 4
Controller Select I/O
Step by step:
1.
Select Configuration from the navigation icons
2. Select I/O allocation settings
3. Select Analog inputs
4. Select the input connected to the sensor (e.g. UI1) as position for Room temperature 1/2/3/4
5. Repeat step 4 for any remaining room temperature sensors.
4.4.4 Operation settings
Adjust the room temperature setpoint in the Data & Settings > Temperature control > Room controller
menu.
Adjust limits for the supply air controller in the Data & Settings > Temperature control > Supply air con-
troller menu.
Overview:
Data & Settings > Temperature Control > Room
controller
04 Apr 13:54
Setpoint room
22.0 °C
Data & Settings > Temp Control > Supply air
controller
04 Apr 13:54
Min limit supply air
14.0 °C
Max limit supply air
30.0 °C