Configuration Manual
Version Document 
A
001 
A
ccess V4.X Configuration manual 
   9 (56)  2018-07-11 
Supply air temperature sensor 
 No 
 Yes 
Summer/Winter setpoints 
 No 
 Yes 
A special summer main setpoint (Supply/Extract/Room) can be activated by 
entering a supply setpoint at summer time: 
External setpoint device 
 No 
 TG-R4-PT100 
 TBI-PT1000 
An external setpoint device, e.g. TBI-PT1000 or TG-R4/PT1000 can be connected. 
The setpoint device must follow the PT1000 resistance curve. The unit is 
connected to the analogue input signal ”External setpoint device”. 
Control input switch Summer/winter 
 No 
 Yes 
To control from BMS system if the building should be in Summer or Winter control 
mode. This is then controlled via Digital input 
Cooling recovery mode 
 Off 
 On 
If the cooling recovery has been configured, there is a cooling requirement and the 
extract air temperature is a settable amount lower than the outdoor temperature, 
cooling recovery can be activated. When cooling recovery is activated the heat 
exchanger and damper sequence output signal will be activated in the cooling 
demand. The function also activates the heating function “Free heating”: if heating 
is required and the outdoor temperature is higher than the extract air temperature, 
outdoor air will primarily be used. 
Cooling recovery Limit 
  Difference limit value 
Temperature difference between Extract air and Outdoor (intake) air. 
Temperature compensation related fan speed 
 None 
 Low 
 High 
  Low & High 
Setpoint adjustement for Low speed and/or high speed. 
Operation settings:  Data & Settings > Temperature control 
Setpoint Cascade controller (extract/room) 
Setpoint adjustments (outdoor temp compensation, fan speed compensation etc.) 
Setpoint Supply controller, min/max-limits and setpoint adjustments 
Setpoint Extra controller 
Settings Supply controller sequence 
Settings heating/cooling pump & pump-kick 