Configuration Manual
Version Document 
A
001 
A
ccess V4.X Configuration manual 
   29 (56)  2018-07-11 
Minimum time for support control and demand control
 20 min 
Extract air fan running during support control
 No 
 Yes 
Operation settings:  Data & Setings > Demand control > Support Control 
Support control is normally used when room temperature control or extract air control 
has been configured. When extract air control is configured a room sensor must be 
installed. “Support control Heating” or “Support control Cooling” will run if Support 
control is configured, the running mode is in Off-state (timer control OFF and not in 
extended running) and if conditions call for support control (see below). Minimum run 
time is settable 0 to 720 minutes (FS= 20 minutes). 
Support control can also be configured when supply air temperature control is used, if 
a room sensor is installed. The controller uses the configured min. (FS=15°C) and 
max. (FS=30°C) limitation values as support control setpoints. However, in this case 
the min. and max. limitation values cannot be changed. To change the values, 
temporarily configure room control, change the min. and max. values and then change 
back to supply air control. 
Support control can also be configured to start only with the supply air fan. In this 
mode, the extract air fan is not active. This requires a digital output to be configured, 
which controls the recirculation damper to open completely so the supply air fan can 
circulate the air to and from the room. The digital output is called “recirculation 
damper”. 
Support control heating 
Demand for support control heating is when the room temperature is lower than the 
start value which is settable 0 to 30°C. The fans will run at the preset speed, the 
heater and the heat exchanger are controlled by the supply air temperature controller 
with the configured max limitation for the supply air (FS=30°C) as setpoint and the 
cooling is shut off (0%). Support control heating stops when the room temperature 
rises to the stop value and the minimum run time has been exceeded or the running 
mode changes to ”On”. 
Support control cooling 
Demand for support control cooling is when the room temperature is higher than the 
start value which is settable 20 to 50°C. The fans will run at the preset speed, the 
heater and the heat exchanger are shut down (0 %) and the cooling is controlled by 
the supply air temperature controller with the configured minimum limitation (FS=15°C) 
as setpoint. Support control cooling stops when the temperature falls below the stop 
value and the minimum run time has been exceeded or the running mode changes to 
”On”. 
  CO2 control 
Activate:  Configuration > Function Configuration > Function Activation 
 Off 
 Start/Stop function 
  Mixing damper function 
  Both start/stop and mixing 










