Communication Manual
Table Of Contents
  Chapter 2 │System integration  6 
Chapter 2 System integration 
Modbus 
Addresses 
All addresses starts with 0, and due to that some Master devices starts address with 1 (equal to register) 
it’s in that case necessary to add all addresses in this document with +1. 
Communication limitations 
The Modbus master must wait for a minimum of 3.5 character times (4 ms at 9600 bps) between two 
messages. 
Baudrate 
9600, 14 400, 19 200, 28 800, 38 400, 57 600, 76 800, 115 200 bps 
Scale factor Modbus 
Real signals could have scale factor according to Scale factor column in tables. In general 10 is used 
except for time setting signals which have scale factor 100, and air flow signals which have scale 
factor 1. Example, with a scale factor 10 of an temperature Integer value could then be interpreted as 
a value with one decimal. Integer, Index and Logic always have scale factor 1. 
Unit 
Real signal values could have an engineering unit according to Unit-column in tables, where T, Q and 
P  represent  temperature-,  flow-  and  pressure  unit  according  selected  preference  setting  in  the 
controller. 
Modbus wiring, etc. 
A  protocol  like  Modbus consists  of  several  layers (OSI-model).  The  bottom layer  is always  the 
physical layer; the number of wires and signal levels. The next layer describes the communication 
digits (number of data bits, stop-bits, parity etc). Next are the layers describing the Modbus-specific 
functions (number of digits per message, the meaning of different messages, etc.). 
For Modbus, the bottom layer can be RS485, RS422, RS232 or Modbus TCP. 
Max. 47 registers 
A maximum of 47 registers can be read in one message. 
Transmission mode 
Access uses the RTU transmission mode for the communication ports. The transmission mode must 
be  the  same  in  the  master  unit  and  the  slave  units,  since  Modbus/RTU  cannot  understand 
Modbus/ASCII messages. The configuration parameter Word length is always 8 for Modbus/RTU. 










