Mixing dampers (Recirculation and/or Recirculation 2 dampers) 
Control 
The analogue output signal (”Recirculation 1” & “Recirculation 2”), control two 
dampers in separate sequence (“Recirculation 1” & “Recirculation 2”) for gradual 
mixing of outdoor air and recirculated air. In this mode the output signal decreases 
with increasing heat demand. 
CO2 
If Recirculation and CO2 controlled ventilation is activated in combination with mixing 
dampers, and the CO2-value rises above the setpoint value, the dampers will let in 
more outdoor air. The function is controlled by a PID-controller. Factory settings: P-
band 100ppm and I-time 100 seconds. These values can bee changed under menu 
PID-controllers. 
3.5 Fan heating/cooling 
Activate:  Configuration > Function Configuration > Function Activation> Sequence Configure 
type 
Example:  Order heating sequence: 
1. ”Exchanger” 
2. ”Heating” 
3. ”Fan heating/cooling”” 
Sequence  Heating  Cooling  Start 
Heating 
Start 
Cooling 
Sequence name 
Sequence-A 2 Off 0% 0% Heating 
Sequence-B 1 1 0% 0% Exchanger 
Sequence-C Off 2 0% 0% Cooling 
Sequence-D Off Off 0% 0% Recirculation 1 
Sequence-E Off Off 0% 0% Recirculation 2 
Sequence-F  3 Off  Off 0% 0% Fan heating/cooling 
Sequence-G Off Off 0% 0% Heating 2 
Sequence-H Off Off 0% 0% Cooling 2 
Sequence-I Off Off 0% 0% Exchanger extract 
Sequence-J  Off  Off  0%  0%  Extra heating/cooling capacity 
Configure:  Configuration > Function Configuration > Function Activation> Sequence Configure 
type > Fan heating/cooling 
Operation settings:  Data & Settings > Temperature control > Fan heating/cooling 
It is possible to select whether the compensation (0...10000) should increase or 
decrease the fan setpoint. The 0...10000 compensation follows the current control 
quantity for the fans. 