Quick configuration guides |
23
Configuration >... > Analog outputs > Cooling (SEQ-C)
24 Jun 10:31
Range output
0–10 V
Configuration > I/O allocation settings > Digital
outputs
24 Jun 10:31
Digital outputs
Device Position
Cooling start (SEQ-C)
Controller DO4
Step by step:
1.
Select Configuration from the navigation icons
2. Select I/O allocation settings
3. Select Digital inputs
4. Select the input connected to the cooler’s feedback contact (e.g. UI4) as position for Feedback cooling (SEQ-C)
5. Select I/O for Run indication DX-compressor (SEQ-C)
6. Go back to I/O allocation settings (use the navigation path Configuration > I/O allocation
settings)
7. Select Analog outputs
8. Select the analog output connected to the cooler control signal (e.g. AO4) as position for Cooling (SEQ-C)
9. Select Cooling (SEQ-C)
10.Adjust Range output to fit with the signal range of the external cooler (e.g. 2-10 V)
11.Go back to I/O allocation settings (use the navigation path Configuration > I/O allocation
settings)
12.Select Digital outputs
13.Select the digital output connected to the cooler (e.g. DO4) as position for Cooling start (SEQ-C).
157618 | A008