Configuration Manual
Version Document 
A
001 
A
ccess V4.X Configuration manual 
   33 (56)  2018-07-11 
When the room temperature has fallen 1 K below the set max limit, recirculation 
will start again if the start conditions are still fulfilled. 
Frequency controlled fans and using recirculation control you can, depending on 
the type of fan control, configure a special pressure/flow offset for the setpoint or a 
manual output signal for the supply air fan. 
  Fire/Smoke 
Activate:  Configuration > Function Configuration > Function Activation 
 No 
 Fire 
 Smoke 
 Fire+Smoke 
Fan settings for Fire function 
Configure:  Configuration > Function Configuration > Fire/Smoke > Fans 
Operation mode when fire alarm 
 Stopped 
 Continuons run 
  Running via normal start/stop conditions 
  Supply air fan run 
  Extract air fan run 
Supply air fan setpoint type when fire alarm 
 Off/Auto normal setpoint 
 Manual setpoint 
 Manual outputs 
  Low speed setpoint 
  Normal speed setpoit 
  High speed setpoint 
Manual setpoint or output (supply air fan) 
 0..100% 
 0.. 
Extract air fan setpoint type when fire alarm 
 Off/Auto normal setpoint 
 Manual setpoint 
 Manual outputs 
  Low speed setpoint 
  Normal speed setpoit 
  High speed setpoint 
Manual setpoint or output (Extract air fan) 
 0..100% 
 0.. 
Fire damper 
Configure:  Configuration > Function Configuration > Fires/Smoke > Fire damper 
Mode 
 Not active 
  Dampers normally closed 
  Damper normally opened 
Test 
 No test 
  Test with unit running 
  Test with unit stopped 