Configuration Manual
Version Document 
A
001 
A
ccess V4.X Configuration manual 
   12 (56)  2018-07-11 
transmitter (“Flow supply air”) is placed in the supply air fan cone, providing a 
measurement of the supply air flow. 
The supply air fan is controlled using the extract air flow as a setpoint. A scaling 
factor can be added if the supply air fan does not have the same characteristics as 
the extract air fan. 
Configure:  Configuration > Function Configuration > Fan control 
Fans 
 Supply+Extract 
 Supply 
 Extract 
Flow presentation 
 No 
 Yes 
Possibility to showing current flow on both fans even when pressure control or 
slave control is used. 
Alarm / Run indication 
Digital input signals are used to supervise fans. They can be configured either for 
indication of the motor running or for monitoring of motor alarm contacts. 
An input configured for run indication should normally be closed during operation. 
Open input when the motor is running, i.e. motor control output is activated, will 
generate an alarm. 
For supply air fans and extract air fans, there is also a conflict alarm, i. e. an alarm 
if the run indication input is closed even though the motor control output is not 
activated. 
An input configured as motor protection should be normally open, i. e. closed 
contact when the motor is running, i.e. motor control output is activated, will 
generate an alarm. 
When running frequency controlled fans, the pressure signal from each respective 
fan’s pressure transmitter is normally used as run indication signal. If the pressure 
falls below the set value during normal operation, a malfunction alarm is activated. 
Alarm from frequency converter 
When running frequency controlled fans, you sometimes want to use both a 
pressure signal from a pressure transmitter and a digital alarm signal from a 
frequency converter. An analogue input for a pressure transmitter and a digital 
input for "Monitoring supply air fan" or "Monitoring extract air fan" must then be 
configured. The setting Fan indication "Run indication/Alarm” on supply and 
extract air fan must be set to "Alarm". A fan alarm will be activated both when 
there is no pressure signal from the pressure transmitter, and when the digital 
signal " Monitoring supply air fan " or " Monitoring extrct air fan " is activated. 
Supply air fan indication 
 None 
 Alarm 
 Run indication 
Extract air fan indication 
 None 
 Alarm 
 Run indication 