Configuration Manual
Version Document 
A
001 
A
ccess V4.X Configuration manual 
   27 (56)  2018-07-11 
  Fan compensation 
Activate:  Configuration > Function Configuration > Function Activation 
Fan compensation 
 No 
 Yes 
Enables the fan compensation via temperature, pressure, CO2, RH sensor. 
There are 3 different compensation curves to use in the sub menu. 
Configure: Configuration > Function Configuration > Fan compensation 
There are three compensation functions called Fan compensation curve 1-3. 
Which can be used to set a compensation based on the configured analogue input 
signal (temperature, pressure, flow humidity, CO2). The curve has three 
parameter pairs which correspond to the value of the compensation at three 
different temperatures. 
The compensation can be selected to apply to both fan or only one of the fan, to 
slow, normal, high or all speeds and only when defrosting. 