Configuration Manual
Version Document 
A
001 
A
ccess V4.X Configuration manual 
   32 (56)  2018-07-11 
Configure:  Configuration > Function Configuration > Recirculation 
Enable supply air temperature control when recirculation running 
 No temperature control 
 Heating/cooling 
 Heating 
 Cooling 
Enable the night cooling function when recirculation 
 No 
 Yes 
Use Extra time channel 4 to start recirculation run 
 No 
 Yes 
Exhaust air fan operation during recirculation run 
 Not running 
 Running 
Fixed setpoint or setpoint adjustment when recirculation run 
 Fixed setpoint 
 Setpoint adjustment 
Operation settings:  Data & Settings > Demand control > Recirculation 
Recirculation is a function for distributing the air in the room using the supply air 
fan. The function can be used even when there is no heating or cooling demand. 
When using recirculation control, the extract air fan stops (but can also be set to 
run) and a recirculation damper opens which allows the air to circulate through the 
unit. 
If timer input for Extended operation is activated during recirculation via “Extra 
timer group 4”, normal/reduced speed gets priority. If timer output for 
normal/reduced speed is activated during recirculation via a digital input, 
recirculation gets priority. 
Analogue output (Recirculation 1 or Recirculation 2) is used as an output signal. 
Recirculation control can be configured as either air circulation (temperature 
control inactive) or air circulation with temperature control. (Only heating, only 
cooling or both heating and cooling). Recirculation control has its own setpoint. 
However, the other settings are the same as for normal operation, i. e. if normal 
operation has been configured as room control, room control will also be used 
during recirculation. 
The recirculation setpoint can be configured as constant or offset. Constant means 
that the recirculation setpoint will be used. Offset is based on an offset from the 
supply air setpoint. 
To lower the temperature, it is possible to configure free cooling to be used during 
recirculation, if the conditions for free cooling are fulfilled. Then, the recirculation 
damper closes, the supply and extract air dampers open and the extract air fan 
starts (the supply air fan also starts, if it is not already running). If the free cooling 
function is not configured for recirculation control and you want to cool down the 
supply air via a low recirculation setpoint, the cooling battery will be used. A max. 
room temperature can be configured for recirculation control. If the room 
temperature rises above the set value (FS 25°C), recirculation will be stopped. 










