PCA 2 1000D OPERATING INSTRUCTION25055055
Table Of Contents
8.1.2 Settings for operation  4.01  +  4.02
SETTING
500 Pa
(22.0 in.wg)
Setpoint 1
Setpoint1
Setting range: in measuring range of sensor 
Factory setting: 50 % of selected measuring range
500 Pa
(2.0 in.wg)
Setpoint 1
Set Internal2
Setting range: in measuring range of sensor 
Factory setting: 50 % of selected measuring range
500 Pa
(2.0 in.wg)
Pband
Pband
Narrow control range =  Short control times
Wide control range = Longer control times and more stable 
control
Setting range: in measuring range of sensor 
Factory setting: 50 % of selected measuring range
0.0 V
Min. Uout
Minimal output voltage
Setting range: 0...10 V (priority over "Max. Uout")
Factory setting: 0 V
10.0 V
Max. Uout
Maximal output voltage
Setting range: 10...0 V
Factory setting: 10 V
Additional menu item for mode 
4.02  with outside-temperature 
dependent target-setpoint  
Operating Instructions PCA-2 1000D2 Programming
L-BAL-E295-GB 1906 Index 001 Part.-No. 
20/48