8.2 Volume sensor  5.00  and volume control  5.01  +  5.02
8.2.1 Base setup  5.00 ...  5.02
BASE SETUP
5.01
Mode
5.00 : Volume flow sensor 
5.01 : Volume flow control 
5.02 : Volume flow control with outdoor temperature compen-
sation 
metric
Units
Display in SI units "metric" (factory setting) or Imperial units 
(US) "inch".
Conversion factors:
Pressure: 1.0 in.wg = 254 Pa
Volume flow: 1.0 cfm = 0.5885 m
3
/h (inlet ring: K-Faktor US = 
9.3 x K-Factor SI) 
Temperature (
4.02 ) t / °F = 1.8 x t °C + 32 
Settings for temperature differences (with SI units in K) are 
also made for Imperial units (US) in °F ( Δ 1.8 °F 
 Δ 1 K ). 
KTY81-210
Temp. Sensor
Temperature sensor for recording the outdoor temperature in 
5.02  operating mode. Sensor type: KTY 81-210 (factory fit-
ted) or PT 1000. 
0...1000 Pa
Measuring 
range
1: 0...1000 Pa (0...4.0 in.wg)
2: 0...500 Pa (0...2.0 in.wg)
3: 0...300 Pa (0...1.2 in.wg)
4: 0...200 Pa (0...0.8 in.wg)
Adjustable measuring range
75
K-Factor
(697 US)
K-Factor US
Nozzle coefficient (K-Factor) 
 following table 
Operating Instructions PCA-2 1000D2 Programming