MODBUS LITE V5.01 parameter specification
Table Of Contents
- 1 Frame protocol
 - 2 Holding Register
- 2.1 Overview
 - 2.2 Reset
 - 2.3 Default set value
 - 2.4 Password
 - 2.5 Control default setting
 - 2.6 Control customer setting
 - 2.7 Operating hours counter
 - 2.8 Operating minutes counter
 - 2.9 Fan address
 - 2.10 Source set value
 - 2.11 Preferred running direction
 - 2.12 Save set value
 - 2.13 Internal parameter set
 - 2.14 Control mode
 - 2.15 Control parameters
 - 2.16 Maximum modulation level
 - 2.17 Minimum modulation level
 - 2.18 Enable motor stop
 - 2.19 Set value (EEPROM)
 - 2.20 Starting modulation level
 - 2.21 Maximum permissible modulation level
 - 2.22 Minimum permissible modulation level
 - 2.23 Maximum speed
 - 2.24 Maximum permissible speed
 - 2.25 Ramp-up curve / ramp-down curve
 - 2.26 Limit speed
 - 2.27 Potentiometer characteristic
 - 2.28 Control limitation
 - 2.29 Maximum power
 - 2.30 Maximum coil current
 - 2.31 Limiting speed for running monitor
 - 2.32 Interface settings
 - 2.33 Shedding function
 - 2.34 Relay dropout delay
 - 2.35 Fail safe function on/off
 - 2.36 Fail safe function set value
 - 2.37 Fail safe function time lag
 - 2.38 Fail safe function running direction
 - 2.39 Potentiometer characteristic limiting value for cable break
 - 2.40 Sensor
 - 2.41 Customer data
 - 2.42 Error history
 - 2.43 Reference value of DC-link voltage
 - 2.44 Reference value of DC-link current
 - 2.45 Production data
 
 - 3 Input Register
- 3.1 Overview
 - 3.2 Identification
 - 3.3 Maximum number of bytes
 - 3.4 Software name of bus controller
 - 3.5 Software version of bus controller
 - 3.6 Software name of commutation controller
 - 3.7 Software version of commutation controller
 - 3.8 Actual speed
 - 3.9 Motor status
 - 3.10 Warning
 - 3.11 DC-link voltage
 - 3.12 DC-link current
 - 3.13 Module temperature
 - 3.14 Motor temperature
 - 3.15 Interior electronics temperature
 - 3.16 Current direction of rotation
 - 3.17 Current modulation level
 - 3.18 Current set value
 - 3.19 Sensor actual values
 - 3.20 Current parameter set
 - 3.21 Current power
 
 
MODBUS parameters "ebm-papst series 84 / 112 / 150 / 200" 
_______________________________________________________________________________________ 
ebm-papst Mulfingen GmbH & Co. KG 
Bachmühle 2 ·74673 Mulfingen, Germany ·Phone: +49 (0) 7938/81-0 ·Fax: +49 (0) 7938/81-110 ·www.ebmpapst.com ·info1@de.ebmpapst.com 
DocNo.: 634505DocNo.: 446144DocNo.:358982DocNo.:322523DocNo.:309753DocNo.:303997DocNo.:276241DocNo.:256078DocNo.:196392 ·Template: 2 dated 6 October 2003 ·File: ext001157859.doc ·Last printed 10/03/2015 15:13:00 
·Page 26 of 70 
Form 1003 
MODBUS 
address 
Designation 
Write 
ebm-papst 
Write 
customer 
Write 
end customer 
Default 
address 
Cust. setting 
address 
(par. 2) 
D13E 
Potentiometer characteristic point 2 X-coordinate 
(par. 2) 
X 
X 
X 
D2BE 
D23E 
D13F 
Potentiometer characteristic point 2 Y-coordinate 
(par. 2) 
X 
X 
X 
D2BF 
D23F 
 D140 - 
D143 
No function 
X 
X 
X 
 D2C0 - 
D2C3 
 D240 - 
D243 
D144 
No function 
X 
X 
- 
D2C4 
D244 
D145 
Limiting speed for running monitor 
X 
X 
- 
D2C5 
D245 
D146 
Reserved 
X 
- 
- 
D2C6 
- 
D147 
No function 
X 
X 
X 
D2C7 
D247 
D148 
No function 
X 
X 
X 
D2C8 
D248 
D149 
Transfer rate 
X 
X 
- 
D2C9 
D249 
D14A 
Parity configuration 
X 
X 
- 
D2CA 
D24A 
D14B 
No function 
X 
- 
- 
D2CB 
- 
D14C 
No function 
X 
- 
- 
D2CC 
- 
D14D 
Motor temperature at start of derating 
X 
X 
- 
D2CD 
D2CD 
D14E 
Motor temperature at end of derating 
X 
X 
- 
D2CE 
D2CE 
D14F 
No function 
X 
- 
- 
D2CF 
- 
D150 
Shedding function 
X 
X 
- 
D2D0 
D250 
D151 
Max. starting modulation level 
X 
- 
- 
D2D1 
- 
D152 
Number of start attempts 
X 
X 
- 
D2D2 
D252 
D153 
Relay dropout delay 
X 
X 
X 
D2D3 
D253 
D154 
No function 
X 
- 
- 
D2D4 
- 
D155 
Maximum power 
X 
X 
- 
D2D5 
D255 
 D156 - 
D15A 
Vacant 
X 
X 
X 
 D2D6 - 
D2DA 
 D256 - 
D25A 
D15B 
Fail safe function running direction 
X 
X 
- 
D2DB 
D25B 
D15C 
Fail safe function on/off 
X 
X 
- 
D2DC 
D25C 
D15D 
Set value for fail safe function 
X 
X 
- 
D2DD 
D25D 
D15E 
Fail-safe dropout delay 
X 
X 
- 
D2DE 
D25E 
D15F 
Potentiometer characteristic limiting value for 
cable break 
X 
X 
- 
D2DF 
D25F 
D160 
D161 
Minimum sensor value 
X 
X 
X 
D2E0 
D2E1 
D260 
D261 
D162 
D163 
Maximum sensor value 
X 
X 
X 
D2E2 
D2E3 
D262 
D263 
 D164 -  
D169 
Sensor unit 
X 
X 
X 
 D2E4 - 
D2E9 
 D264 - 
D269 
 D16A - 
D16F 
Vacant 
X 
X 
X 
 D2EA - 
D2EF 
 D26A - 
D26F 
 D170 - 
D17F 
Customer data 
X 
X 
- 
 D2F0 - 
D2FF 
 D270 - 
D27F 
D180 
Operating hours counter 
X 
- 
- 
- 
- 
D181 
Operating minutes counter 
X 
- 
- 
- 
- 
D182 
Error indicator 
X 
- 
- 
- 
- 
D183 
Vacant 
X 
- 
- 
- 
- 
D184 
1st error 
X 
- 
- 
- 
- 
D185 
1st error timing 
X 
- 
- 
- 
- 
 D186 - 
Error history 
X 
- 
- 
- 
- 