3 Product overview
3.1 Function
Sensor-control module with differential-pressure sensors in proven 
ceramic-cantilever technology for climate and clean-room applica-
tion.
The pressure range goes from 0...1000 Pa (0...4.0 in.wg), four 
measuring ranges are programmable.
Function when the pressure at the “Plus”- connection exceeds the 
pressure at the “Minus”- connection. 
Depending on the programmed Mode the device can be used 
as sensor or as a control module for pressure or volume flow.
•
For operation as pressure sensor the device supplies an output 
signal (0...10 V) proportional to the measuring range.
•
For operation as volume flow sensor the device supplies an 
output signal (0...10 V) proportional to the air volume measuring 
range (see INFO / Range qV). Function in combination with 
centrifugal fans and measuring device in the inlet ring. The 
controller calculates the volume flow of the fan from the “K-
Factor” and pressure differential between the suction side and 
the inlet duct. 
•
For operation as control module for pressure or volume flow the 
purpose of the device is to reach and maintain the target value 
set. To accomplish this, the measured actual value (sensor 
value) is compared with the adjusted target value, and the con-
trolled value is deduced from this. Controlled output (0...10 V) 
e.g. for activating a speed controller for fans or an EC-fan 
directly.
Operating Instructions PCA-2 1000D2 Product overview