PCA 2 1000D OPERATING INSTRUCTION25055055
Table Of Contents
Mode Function
5.02
Volume flow control (PID) with outdoor temperature compensation: 
output 0...10 V depending on adjusted setpoint, outdoor temperature 
and measured actual value.
7.2 Start-up
Procedure
1. You  must  mount  and  connect  the  device  in  accordance  with 
the operating instructions.
2. Double check that all connections are correct.
3. The  supply  voltage  must  match the  information on the  rating 
plate.
4. Set the mode, unit and measuring range and adjust the sensor 
in the BASE SETUP.
5. Set the parameters for control operation for the modes 
4.01 , 
4.02 ,  5.01 ,  5.02  unter "SETTING".
7.3 Menu structure
100 Pa
Δp
Display after turning on the voltage supply.
Switch over between actual value display and 
“INFO” with the key shortcut for Escape (Esc 
= ▼ + ▲ ).
INFO 
Selection of the menu group (e.g. BASE SETUP) to the right 
through the ▼-key, to the left through the ▲-key. 
Youcangotothemenuitemsinthemenugroups (e.g. mode) by using 
the P key. Use the arrow keys to move up and down within the 
menu group. 
To make adjustments, press the P key after selecting the menu 
item. If the previously set value starts to flash, it can be adjusted 
with the ▼ + ▲ keys and then saved with the P key. To exit the 
menu without making any changes, use the “Esc” short-key, i.e., 
the originally set values remain.