MODBUS LITE V5.01 parameter specification

Table Of Contents
MODBUS parameters "ebm-papst series 84 / 112 / 150 / 200"
_______________________________________________________________________________________
ebm-papst Mulfingen GmbH & Co. KG
Bachmühle 2 ·74673 Mulfingen, Germany ·Phone: +49 (0) 7938/81-0 ·Fax: +49 (0) 7938/81-110 ·www.ebmpapst.com ·info1@de.ebmpapst.com
DocNo.: 634505DocNo.: 446144DocNo.:358982DocNo.:322523DocNo.:309753DocNo.:303997DocNo.:276241DocNo.:256078DocNo.:196392 ·Template: 2 dated 6 October 2003 ·File: ext001157859.doc ·Last printed 10/03/2015 15:13:00
·Page 47 of 70
Form 1003
2.30 Maximum coil current
Address : D13B
Write authorisation : ebm-papst
Encoding:
][
170
][max, AIzeferenceR
bytes Data
AeffI
Ref. Iz ................ DC-link current reference variable (see 2.44 Reference value of DC-link current)
The MSB is of no relevance!
If the function has been activated in the "Control limitation" parameter, the motor will limit the coil current
(effective value) to the value specified here (see 2.28 Control limitation).
The coil current is made up of the DC-link current / modulation level
2.31 Limiting speed for running monitor
Address : D145
Write authorisation : ebm-papst, customer
Encoding:
The limit speed for the running monitor is made up of the parameter and the maximum speed:
]rpm[
64000
]rpm[ nMax
bytes Data
monitor running for speedLimit
nMax [rpm] to maximum speed (in rpm) - see 2.23 Maximum speed
If the actual speed (see 3.8 Actual speed) is less than the limiting speed for the running monitor, the error
relay will trip. The "n_Low" flag is set in the "Warning" input register (see 3.10 Warning)
If "Limiting speed for running monitor" = 0, the entire function is deactivated.