PCA 2 1000D OPERATING INSTRUCTION25055055

OFF
Autozero
If the actual value is not 0 Pa Δp in pressureless state a
zero-point adjustment is possible with fuction Autozero.
This may be necessary, for example, in case of heavy ther-
mal uctuations in the sensor environment or non-vertical
mounting.
Proceed as follows:
1. Pull off the pressurised hoses.
2. Switch function Autozero to ON.
3. The display switches to the actual value display and the
value 0 is displayed after zero point calibration has
taken place.
4. The necessary difference up to 0 is displayed in the
BASE SETUP under Offset.
0 Pa
(0.000 in.wg)
Offset
Alternatively to the automatic zero point calibration, the offset
value can also be set manually.
Setting range: +/ - 1000 Pa (+/- 4.000 in.wg)
0.0 K
(0.0 °F)
Offset
Offset temperature sensor for mode
5.02 .
Setting range: -20.0...20.0 °C (-36.0...36.0 °F)
Factory setting: 0.0 K (0.0 °F)
OFF
Factory Setting
Attention!
ON => restore factory setting = delivery status
(xxx) Values for Imperial units (US)
8.2.2 Nozzle coefcient (K-Factor)
Maximum K-Factor depending on the measuring range of the pressure sensor
Range [Pa]
Range [in.wg]
200
0.8
300
1.2
500
2.0
1000
4.0
Max. K-Factor
Max.US
4596
32767
3752
32767
2906
32767
2055
32500
Air volume measuring range [m
3
/h], [cfm] depends on selected
measuring range of pressure senosr [Pa], [in.wg] and selected K-
Factor (US). In menu INFO display for Range qV. Maximum
measuring range at input of each possible maximum K-Factor
(US).
Operating Instructions PCA-2 1000D2 Programming
L-BAL-E295-GB 1906 Index 001 Part.-No.
23/48