PCA 2 1000D OPERATING INSTRUCTION25055055
Table Of Contents
OFF
Autozero
If the actual value is not “0 Pa Δp” in pressureless state a
zero-point adjustment is possible with fuction “Autozero”.
This may be necessary, for example, in case of heavy ther-
mal fluctuations in the sensor environment or non-vertical
mounting.
Proceed as follows:
1. Pull off the pressurised hoses.
2. Switch function “Autozero” to “ON”.
3. The display switches to the actual value display and the
value “0” is displayed after zero point calibration has
taken place.
4. The necessary difference up to “0” is displayed in the
BASE SETUP under “Offset”.
0 Pa
(0.000 in.wg)
Offset
Alternatively to the automatic zero point calibration, the offset
value can also be set manually.
Setting range: +/ - 1000 Pa (+/- 4.000 in.wg)
0.0 K
(0.0 °F)
Offset
Offset temperature sensor for mode
5.02 .
Setting range: -20.0...20.0 °C (-36.0...36.0 °F)
Factory setting: 0.0 K (0.0 °F)
OFF
Factory Setting
Attention!
ON => restore factory setting = delivery status
(xxx) Values for Imperial units (US)
8.2.2 Nozzle coefficient (K-Factor)
Maximum K-Factor depending on the measuring range of the pressure sensor
Range [Pa]
Range [in.wg]
200
0.8
300
1.2
500
2.0
1000
4.0
Max. K-Factor
Max.US
4596
32767
3752
32767
2906
32767
2055
32500
Air volume measuring range [m
3
/h], [cfm] depends on selected
measuring range of pressure senosr [Pa], [in.wg] and selected “K-
Factor (US)”. In menu “INFO” display for “Range qV”. Maximum
measuring range at input of each possible maximum “K-Factor
(US)”.
Operating Instructions PCA-2 1000D2 Programming
L-BAL-E295-GB 1906 Index 001 Part.-No.
23/48