1&2 Installation manual
 Systemair  
 CO2  Duct Mount Sensors 
 User Instructions 
 4.  Connect the conduit and make necessary wire connections. 
  Figure 3: Wiring 
 Figure 1: Systemair-1 CO2 duct sensor Installation 
T63361-001 
Oct 2012 
  Page 1 of 3 
  The Duct Mount CO
2 Sensors
are transmitters designed to be 
                                                                                    installed in HVAC return air 
  ducts. The technology is based 
  on the absorption of light in a 
  gold-plated reflective light pipe 
  or waveguide diffusion gas 
  chamber. A gas permeable 
  PTFE filter prevents particulate 
  and water contamination of the 
  sensor. Light is absorbed in 
  proportion to the CO
2 
  concentration and the 
remaining light is measured and converted into an analog signal. 
Installation Instructions 
1.  Before installing the sensor, note the direction of the airflow. Ensure 
  all mounting holes are sealed tightly. 
2.  Drill/cut one 1-1/2” hole and punch/drill two 1/8” holes for 
  mounting screws. 
3.  Slide the sensor into 1 ½” hole and secure with #10 sheet metal 
  screws.
      Figure 2: Systemair-2 CO2 duct sensor Installation 
5.  Install lid, and ensure it snaps into place. 
Duct Mount CO2 Sensors 