CO2DT R IMOSV FR

INSTRUCTION
i
Read this instruction before installation
and wiring of the product
1
S-CO2DT-R
CO
2
-transmitter for duct mounting
CO2DT-R is a transmitter for measuring carbon dioxide (CO
2
) concen-
tration in exhaust air. Measuring range 0...2000ppm and relay output.
CO2DT-R is intended for duct mounting.
Technical data
Measuring principle NDIR (Non-Dispersive Infrared
Technology)
Measuring range 0...2000 ppm
Inaccuracy at 20°C < ±(50 ppm + 2% of the measured value)
Temp. inuence typ. 2 ppm / K
Long term stability typ. 20 ppm / year
Time constant < 120 seconds
Warm-up time < 5 minutes
Ambient temperature -5...55°C
Humidity 0...90 % RH non condensating
Protection class IP65 with probe downwards, otherwise
IP20
Mounting
CO2DT-R should be mounted at a place in the duct where it can be
expected to give a representative reading. The transmitter should be
placed at least 4 duct diameters after a bend for minimal turbulence.
Open the front cover by removing the screws on the cover with a screw-
driver.
CO
2
sensing element
air flow direction
Wiring
Supply voltage 24 V AC ±20%, 50...60 Hz or 15...35 V DC.
Consumption 3 W.
1 Supply voltage 24 V AC/DC or 15...35 V DC
2 System neutral
3 Common
4 Normally open
5 Normally closed
Hysteresis and level
switching off
ppm
2000
1000500
relay status
switching
on
ON
OFF
Hysteresis [% of measuring range]
Level [% of
measuring range]
25% of
measuring
range
Start-up
After applying power to CO2DT-R, it will take a few minutes before it
shows correct values.
Calibration
CO2DT-R is factory calibrated before delivery and does not need to
be calibrated at installation.
CO2DT-R is calibrated automatically, which means that manual recali-
bration is not required during the lifetime of the sensor.
EMC emission and immunity standards
This product conforms to the requirements of European EMC stan-
dards CENELEC EN 61000-6-1 and EN 61000-6-3 and carries the
CE mark.
Contact
Systemair AB, 739 39 Skinnskatteberg, Sweden
Tel: +46 222 440 00, Fax: +46 222 440 99
www.systemair.com, mailbox@systemair.se
8304C