211599 VTR 700 WATER HEATER INSTALLATION(A001)
Table Of Contents
Configuration |
5
3. Activate the actuator. Go to Components menu, select Heater menu and select type as Water. Choose actuator
voltage type. Do advanced settings if necessary.
4. Configure connection of the actuator. Go to Service menu. Select Output menu. In next menu select ANALOG tab.
Select the analog output to which the actuator is connected. Example if it is connected to AO3 on the connection
board, then select ANALOG OUTPUT 3 and select Y1 Heating from the output type list.
5. Configure frost protection sensor (FPT). Go back to Input menu. Select ANALOG tab. Select the analog input to which
the frost protection sensor is connected. Example if it is connected to AI4 on the main circuit board, then select ANA-
LOG INPUT 4 and select Frost Protection Temperature Sensor (FPT) from the input type list.
211599 | A001