INSTALLATION ODS TOPVEX SR 135577 A003

Warnings
|
1
1 Warnings
Danger
Make sure that the mains power supply to the unit is disconnected before performing any maintenance
or electrical work!
All electrical connections must be carried out by an authorized installer and in accordance with local rules
and regulations.
Warning
The door handles are only intended to be used during the installation and service. These must be
removed before the unit is put into operation to ensure the required level of safety for the unit.
The unit must be duct connected or in some other way provided with protection so that it is not possible
to come in contact with the fans through the duct connections
The unit is heavy. Be careful during transport and mounting. Risk of injury through pinching. Use
protective clothing.
Beware of sharp edges during mounting and maintenance. Make sure that a proper lifting device is used.
Use protective clothing.
The units electrical connection to the mains supply must be preceded by an all pole circuit breaker with a
minimum 3 mm gap.
Caution
If the unit is installed in a cold place make sure that all joints are covered with insulation, and tape well
Duct connections/duct ends should be covered during storage and installation
Do not connect tumble dryers to the ventilation system
Take care not to damage the water battery when connecting water pipes to connectors. Use a spanner to
tighten the connection.
2 Mounting ODS
ODS installation procedure; examples show left hand unit.
Parts enclosed with the ODS Parts not enclosed with the ODS
8 pcs allen bolts M5x16
Dampers
For Topvex SR03–06 20 pcs sheet tracs M4x9.5
For Topvex SR09–11 32 pcs sheet tracs M4x9.5
8 pcs M8x20 hex bolt (for the dampers)
For Topvex SR09–11 4 pcs hex bolts M10x70 Tools
2 pcs offset parts
16 pcs M6x20
2.1 Topvex SR03–06
1 Mount the two offset parts on the exhaust air side.
2 Mount the damper on to the offset parts. Make sure
that the offset parts are in the correct angel to make
space for the damper motor.
135577 | A003