Manual FCR230 Modbus/BACnet

6
Input register
Name of signal Type
Modbus
address
Description
RC_Actual_X.RegioSoftware X,4 1 Type of Regio software:
0 = RCP
1 = RC
RC_Actual_X.RegioVerMajor X,4 2 Major version
RC_Actual_X.RegioVerMinor
X,4
3
Minor version
RC_Actual_X.RegioVerBranch X,4 4 Branch version
RC_Actual_X.RegioRevision X,4 5 Revision
Not used in this model X,4 6
RC_Actual_X.RegioUnitState X,4 7 Current running mode:
0 = Off
1 = Economy/Standby
2 = Not used
3 = Not used
4 = Comfort
RC_Actual_X.RegioControllerState X,4 8 Current control:
0 = Off
1 = Heating
2 = Cooling
RC_Actual_X.RegioFanSpeed X,4 9 Current fan speed:
0 = Off
1 = Fan speed 1 active
2 = Fan speed 2 active
3 = Fan speed 3 active
Not used in this model X,4 10
RC_Actual_R.RegioRoomTemp R,4 11 Room temperature
RC_Actual_R.RegioRoomTempExt R,4 12 Room temperature from external sensor
RC_Actual_R.RegioRoomTempInt
R,4
13
Room temperature from internal sensor
RC_Actual_R.RegioAIChangeOver R,4 14 Change-over temperature
RC_Actual_R.RegioAnaIn1 R,4 15 Value on analogue input 1
RC_Actual_R.RegioUAnaIn1 R,4 16 Value on universal analogue input 1
RC_Actual_R.RegioUAnaOut1 R,4 17 Value on universal analogue output 1
RC_Actual_R.RegioUAnaOut2
R,4
18
Value on universal analogue output 2
Not used in this model 19
RC_Actual_R.RegioPIDSetP R,4 20 Controller setpoint
RC_Actual_R.RegioPIDOutput R,4 21 Controller output signal (0…100 %)
RC_Actual_R.RegioHeatOutput R,4 22 Heating output signal (0…100 %)
RC_Actual_R.RegioCoolOutput
R,4
23
Cooling output signal (0…100 %)
RC_Actual_R.RegioAI1Raw R,4 24 Raw value for analogue input 1
RC_Actual_R.RegioUI1Raw R,4 25 Raw value for universal input 1
RC_Actual_R.RoomTemp_NTC2 R,4 26
Room temperature input value from secondary
internal sensor
RC_Actual_R.RegioSupplyAirTemp R, 4 47 Supply air temperature from sensor connected
to AI1
RC_Actual_R.RegioSupplyAirPIDout
R, 4
48
Supply air controller output
RC_Actual_R.RegioPID2Setp R, 4 49 Room controller output (scaled) and supply air
controller setpoint