Manual FCR230 Modbus/BACnet

5
Coil status register
Name of signal Type
Modbus
address
Default
value
Description
Not used in this model L,1 1 0
RC_Setp_L.RegioShutDown L,1 2 0 Puts the unit in Shutdown mode.
RC_Setp_L.RegioFireAlarmStop L,1 3 0 Places the unit in Shutdown mode and
prevents it from being activated again,
unless this value is first set to “0”.
RC_Setp_L.RegioDiNC(0) L,1 4 0 Not used
RC_Setp_L.RegioDi1NC L,1 5 0 Normally open (NO) or normally closed
(NC) on digital input. 0=NO, 1=NC.
Not used in this model L,1 6 .
RC_Setp_L.RegioUDi1NC L,1 7 0
Normally open (NO) or normally closed
(NC) on universal digital input. 0=NO,
1=NC.
Not used in this model L,1 8 -
RC_Setp_L. RegioDO4NC L,1 9 1 DO4 NO/NC
RC_Setp_L.RegioDO5NC L,1 10 1 DO5 NO/NC
RC_Setp_L.RegioDilAct L,1 11 0 DI1-activation (presence/window)
Economy/Off
RC_Setp_L.RegioMPAct L,1 12 0 Activation of Mould protection.
RC_Setp_L.RegioTermoModel L,1 13 0 EEPROM storage of Thermo model
variable (3-point actuator)
RC_Setp_L.RegioMinFanSpeed L,1 14 1 The fan is run at its minimum speed setting
if the automatic fan control calculates that
the fan can be switched off.
Not used in this model
- 15
-
RC_Setp_L.RegioComFactoryDefaults
L,1 16 0
Set communication parameters to factory
settings (does not apply to addresses):
1 = Factory settings (resets to 0)
RC_Setp_L.RegioBlockConfig
L,1 21 0 Blocks the option to enter the parameter
list using the buttons on RCF.
RC_Setp_L.RegioPreventManualFanSp
eed
L,1 22 0 Prevents the fan speed from being changed
manually if the fan is not set to auto
(parameter 25).