Manual FCR230 Modbus/BACnet
Table Of Contents
14
Object name Object ID Description Unit
Writeabl
e
RC_Setp_R.RegioHeatOutputManual Analog value, 13 Manual value heating
output
% Yes
RC_Setp_R.RegioCoolOutputManual Analog value, 14 Manual value cooling
output
% Yes
RC_Setp_R.RegioRoomTempRemote Analog value, 15 Remote control of room
temperature.
°C Yes
RC_Setp_R.RegioStandbySetPDeadBand Analog value, 16 Deadband for Standby
mode
°C Yes
Not used in this model Analog value, 17-26
RC_Setp_R.RegioMinECFanSpeed Analog value, 27 Lowest possible speed for
the EC fan
% Yes
RC_Setp_R.RegioMaxFanSpeed Analog value, 28 Highest possible speed for
the EC fan
% Yes
RC_Setp_R.RegioAIChangeOverLimitLow Analog value, 29 Cooling if lower change-
over temperature
°C Yes
RC_Setp_R.RegioAIChangeOverLimitHigh Analog value, 30 Heating if higher change-
over temperature
°C Yes
RC_Setp_R.RegioThermostatHyst Analog value, 31
Room temperature
hysteresis
°C Yes
RC_Setp_R.RegioComfortSetPDeadband Analog value, 32 Deadband for comfort
mode.
°C Yes
RC_SetpExt_R.RegioRCFSetPoint Analog Value, 33 Basic setpoint for the
controller
°C Yes
RC_Actual_R.RegioPID2Setp Analog Value, 34 Calculated supply air
setpoint
°C No
Binary inputs
Object name Object ID Description Values Writeable
RC_Actual_L.RegioDIOpenWindow Binary input, 0 Indicates open window
ACTIVE/
INACTIVE
No
Not used in this model Binary input, 1 No
RC_Actual_L.RegioDIPresences Binary input, 2 Indicates presence from
digital input
ACTIVE/
INACTIVE
No
RC_Actual_L.RegioDIChangeOver Binary input, 3 Indicates change-over
from digital input
ACTIVE/
INACTIVE
No
Not used in this model Binary input, 4-6 No
All binary inputs have normal polarity.