Manual FCR230 Modbus/BACnet
Table Of Contents
13
BACnet signals
Analogue inputs
Object name Object ID Description Unit Writeable
RC_Actual_R.RegioRoomTemp Analog input, 0
Room temperature °C No
RC_Actual_R.RegioAIChangeOver
Analog input, 1
Change-over temperature
°C No
RC_Actual_R.RegioAnaIn1
Analog input, 2
Value on analogue input 1
°C No
RC_Actual_R.RegioUAnaIn1
Analog input, 3
Value on universal analogue
input 1
V No
RC_Actual_R.RegioSupplyAirTemp
Analog input, 4
Supply air temperature
°C No
Analogue values
Object name Object ID Description Unit
Writeabl
e
RC_Actual_R.RegioUAnaOut1 Analog value, 0 Value on universal
analogue output 1
V No
RC_Actual_R.RegioUAnaOut2 Analog value, 1 Value on universal
analogue output 2
V No
RC_Actual_R.RegioSetPAdjustment Analog value, 2 Setpoint displacement from
internal unit
°C No
RC_Actual_R.RegioPIDSetP Analog value, 3 Controller setpoint °C No
RC_Actual_R.RegioPIDOutput Analog value, 4 Controller output % No
RC_Actual_R.RegioHeatOutput Analog value, 5 Heating control % No
RC_Actual_R.RegioCoolOutput Analog value, 6 Cooling control % No
Not used in this model Analog value, 7-8 Yes
RC_Setp_R.RegioUnOccSetPHeat Analog value, 9 The room heating setpoint
when in “Economy” mode
°C Yes
RC_Setp_R.RegioUnOccSetPCool Analog value, 10 The room cooling setpoint
when in “Economy” mode
°C Yes
Not used in this model Analog value, 11
RC_Setp_R.RegioSetPOffset Analog value, 12 Setpoint displacement
during presence
°C Yes