MANUAL PTA01
PTA 01
9
Function:
Fan speed and heat output are set on the
PP15 regulator. When the temperature
regulator PTA01 is used, the desired room
temperature is set on the thermostat 4 wich
is placed inside the PTA01 (the internal
thermosat of the fanheater is not in use).
The digital time switch
3 is programmable
on a weekly basis. When the time switch is
in ON-position, day program is active and in
OFF-posistion the night program is active.
For programming of the time switch, see
separate instructions.
Day program:
The desired day temperature is set on the
thermostat with the knob marked ”TEMP”.
Night program:
During the night the desired day tempera-
ture is automatically reduced by 0-10
o
C.
Digital time switch
3
For programming, see separate operating
instructions.
Technical data:
Type: STT-127N
Connection voltage: 230V 50Hz
Max current breakpoint: 10A, 230V AC1
Thermostat
4
The desired day temperature is set on the
thermostat with the knob marked ”TEMP”.
The disired hysteresis is set on the
thermostat with the knob marked ”DIFF” and
is defined as the difference between
connection and disconnection. For optimum
regulation, set the ”DIFF” knob at 0,5.
The desired day temperature reduction is
set on the thermostat with the knob marked
”SETBACK”.
The room sensor is preconnected and
placed in the gland at the bottom to the right
in the housing.
N.B! The room temperature sensor must
extend about 20mm from the cable gland,
wich must be adjusted to obtain correct
regulation.
Technical data:
Type: TM1N/D
Connection voltage: 230V +/-15%,
50-60Hz
Max current breakpoint: 10A 230V AC1
Temp setting: -15 - +30 °C
DIFF : 0,5 - 10K
SETBACK : 0 - 10K
Temp sensor: TG-B130
NTC 0-30 °C
GB
Temperature regulator