MANUAL PSM01
Table Of Contents
Technical Specifications (Cont.)
Feedback Signal
AGD: 135 ohm feedback potentiometer
AGE: 1,000 ohm feedback potentiometer
GGx, HGx: 0 to 10 VDC or 2 to 10 VDC for 90° (10 VDC at 1 mA)
Corresponds to input signal span selection.
JGx: 0 to 10 VDC for 90° (10 VDC at 1 mA)
Auxiliary Switch Rating
xGC: Two Single-Pole, Double-Throw (SPDT) switches rated at 24 VAC
1.5 A inductive, 3.0 A resistive; 35.0 VA maximum per switch, Class 2
Mechanical Output
(Running Torque)
M9108 Series: 70 lb·in (8 N·m) for one unit; not intended for tandem use
M9116 Series: 140 lb·in (16 N·m) for one unit
M9116 (in tandem) 280 lb·in (32 N·m) for two units (GGx, HGx)
M9124 Series: 210 lb·in (24 N·m) for one unit
M9124 (in tandem) 420 lb·in (48 N·m) for two units (AGx, GGx, HGx)
M9132 Series: 280 lb·in (32 N·m) for one unit,
M9132 (in tandem) 560 lb·in (64 N·m) for two units (AGx, GGx)
Audible Noise Rating
45 dBA at 1 m
Rotation Range
0 to 90° in 5-degree increments, mechanically limited to 93°
Rotation Time
M9108: 30 seconds at 50% rated load,
25 to 50 seconds for 0 to 70 lb·in (0 to 8 N·m)
M9116: 80 seconds at 50% rated load
70 to 115 seconds for 0 to 140 lb·in (0 to 16 N·m)
M9124: 130 seconds at 50% rated load
115 to 175 seconds for 0 to 210 lb·in (0 to 24 N·m)
M9132: 140 seconds at 50% rated load
115 to 205 seconds for 0 to 280 lb·in (0 to 32 N·m)
Electrical Connection
M9124-, M9132-AGx:
1/4 in. spade terminals with pluggable 3-terminal blocks
All Other Models: Screw terminals for 22 to 14 AWG; maximum of two 18, 20, or
22 AWG per terminal
Mechanical Connection
3/8 to 3/4 in. (10 to 20 mm) diameter round shaft or a 3/8 to 5/8 in. (10 to 16 mm) square shaft
Enclosure
NEMA 2, IP42
Ambient Conditions
Operating: -4 to 122°F (-20 to 50°C); 0 to 95% RH, noncondensing
Storage: -40 to 186°F (-40 to 86°C); 0 to 95% RH, noncondensing
Dimensions (H x W x D)
7.09 x 3.94 x 2.54 in. (180 x 100 x 64.5 mm)
Shipping Weight
2.9 lb (1.3 kg)
Agency Compliance
UL Listed, File E27734, CCN XAPX
CSA Certified, File LR85083, Class 3221 02
CE Mark, EMC Directive 89/336/EEC
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
Controls Group
507 E. Michigan Street
P.O. Box 423 Printed in U.S.A
.
Milwaukee, WI 53201 www.johnsoncontrols.co
m
8 M9108, M9116, M9124, and M9132 Series Electric Non-Spring Return Actuators Installation Instructions