MANUAL VR2025

Min. 20 mm.
Manuell/Auto omställare
75
75
65
63
Manual/Auto-lever
Min. 20 mm
VR 20/25
12
GB
Actuator on/off (SD20)
Application
The electrical actuator in combination
with the 3-way valve (TRV20/25) is used
for regulating the heat supply to the
unit. It's function is to open or close the
valve (on/off). The actuator will open
the valve when power is applied. The
actuator is "soft closing" just to avoid
noise and pressure blow in the pipe
system.
The electrical actuator can be
mounted and rotated after that the valve
has been installed.
For regulating the actuator in
combination with valve complement
with appropiate thermostat.
Mounting
Never use the actuator as a mounting
lever. Make sure the actuator is free
of thermal insulation connections and
leave at least 20 mm clearance above
the actuator for mounting purposes
according to the figure below.
Technical specifications | SD20
Application
The bypass valve is used when a small
amount flow of water should pass by
the unit at all times. The purpose of
this is that the water should always stay
hot in the watercoil, in cases when a
door opens and a quick heat supply is
needed.
This kind of valve has the dimension
DN10 (3/8").
When mounting the plug inside the
valve must be screwed entirely at first
and then screwed back a whole lap.
In cases where the distance between
inlet and the unit is far away, open the
plug even more by screwing the plug
backwards.
Technical specifications | BPV10
Bypass valve (BPV10)
(193SN38R)
(VA-7010-8103A)
Type Article no. RSK no. HxWxD [mm] Weight [kg]
BPV10 10030 672 76 00 63x45x28 0,17
Type Article no. RSK no. HxWxD [mm] Weight [kg]
SD20 10073 672 70 37 75x75x65 0,5
Action : On/Off
Supply Voltage : 230 V~   -10 % / +15 %
Power consumption : 7 VA
Min. force (nominal) : 150 N   -10 % / +20 %
Stroke (nominal) : 3 mm (max. 5 mm)
Full stroke time "On" : Nominal 10 sec.
Full stroke time "Off" : Nominal 5 sec.
Enclosure : IP40, NEMA 1
Ambient operating condition : +2 
o
C to +50 
o
C
Ambient storage condition : -20 
o
C to +65 
o
C
CE Conformity : EMC Directive 89/336 EU