Application
IR is suitabe for total or supplementary
heating of premises with large volume and
high ceilings. It can also be used outdoors
for example on sport arena stands or to keep
loading bays dry and frostless.
Function
The infrared heater heats up rapidly and
provides additonal heating input immediately
to the area.
Positioning
For point-heating, at least two infra-red
heaters are placed to ensure that heat is
provided both in front of and behind people
involved. The heaters must be mounted at
least 2 m above people´s heads.
Mounting
Suspension brackets can be fitted directly to
the ceiling or wall. The mountings allow the
radiation to be varied 30° in any direction.
Note the permitted installation arrangements
and minimum distances shown on page 4.
In all installations the elements must be
horizontal. It is also possible to suspend the
heaters from cords(minimum Ø 3 mm).
Electrical installation
The apparatus must be permanently
connected. The installation must be carried
out by a qualified technician, and the
appropriate regulations must be followed.
A heat resistant connection cable that can
withstand a constant temperature of at least
90 °C, must be used when connecting the
heater. The connection box contains terminal
blocks for connecting cables with areas up to
16 mm². This makes it possible to connect
several heaters in parallel.
Installation and operating instructions
General Instructions
Read these instructions carefully before
installation and use. Keep this manual for
future reference.
The product may only be used as set out in
the assembly and operating instructions. The
guarantee is only valid if the product is used
in the manner intended and in accordance
with the instructions.
Control
When using this product as a local space
heater according to Ecodesign Regulation
(EU) 2015/1188, it must be supplemented
with one of the following approved controls.
Please note that a relaybox RB is also
required.
TAP16R, electronic thermostat that
includes:
- Electronic room temperature control plus
week timer
- Room temperature control with open
window detection
TAP16R and SKG30, black bulb sensor that
include:
- Electronic room temperature control plus
week timer
- Room temperature control with open
window detection
- Black bulb sensor
RB123, relaybox with 3 step output control
and PDK65, presence detector that include:
- Two or more manual stages, no
temperature control
- Working time limitation
- Room temperature control with presence
detection
The product can be controlled in a different
way, e.g. by an overall control system (BMS),
but in that case the responsibility lies with
the installer to ensure that the control system
is programmed to make the installation meet
the requirements of Ecodesign Regulation
(EU) 2015/1188.
Start-up
When the unit is used for the first time or
after a long period of disuse, smoke or odour
may result from dust or dirt that has collected
on the element. This is completely normal
and disappears after a short time.