User Manual

UL LISTED
ALARM
CONTROL
PANEL
2 – WIRE
SMOKE
ZONE
+
+
AUXILIARY
POWER
OUTPUT
YELLOW
PURPLE
T +
ORANGE
RED
BLACK
BROWN
WHITE
AUXILIARY
RELAY
470
1/2 WATT*
SYSTEM SENSOR
2WTA-B SMOKE
DETECTORS
(UP TO 16 DETECTORS
PER ZONE)
ADEMCO
CONTROL
PANEL
APPCLICABLE
CONTROLS:
5110XM
5140XM
VISTA-32FB
VISTA-100
VISTA-128FB
SYSTEM SENSOR REVERSING
RELAY/SYNCHRONIZATION MODULE (RRS-MOD)
(MOUNT INSIDE CONTROL ENCLOSURE)
NOT REQUIRED ON 5110XM
WHEN 5100XM JUMPER W3 INTACT
TAKE POWER FROM CONTROLS
AUXILIARY POWER OUTPUT ONLY
EOL
2K OHMS
OPTIONAL
REMOTE
ANNUNCIATOR
(RA400Z/RA100Z)
OPTIONAL
REMOTE
ANNUNCIATOR
(RA400Z/RA100Z)
+
1 + IN
2 + OUT
3 - IN/OUT
4 RA+
5 RA-
1 + IN
2 + OUT
3 - IN/OUT
4 RA+
5 RA-
+
*4701/2 WATT RESISTOR NEEDED FOR PANEL TO RESET
ALARM
CIRCUIT
(positive signal
in alarm state)
UL LISTED
ALARM
CONTROL
PANEL
INITIATING
CIRCUIT
PURPLE
T+
+
+
AUX POWER
2 -WIRE
YELLOW
ORANGE
RED
BLACK
BROWN
WHITE
BELL/
470
1/2 WATT*
ADEMCO
CONTROL
PANEL
APPCLICABLE
CONTROLS:
VISTA-20
VISTA-40
VISTA-50P
VISTA-32FB
VISTA-100
VISTA-128FB
SYSTEM SENSOR REVERSING
RELAY/SYNCHRONIZATION
MODULE ( RRS-MOD)
(MOUNT INSIDE CONTROL ENCLOSURE)
SYSTEM SENSOR
2WTA-B SMOKE
DETECTORS
(UP TO 16 DETECTORS
PER ZONE)
EOL
2K OHMS
OPTIONAL
REMOTE
ANNUNCIATOR
(RA400Z/RA100Z)
OPTIONAL
REMOTE
ANNUNCIATOR
(RA400Z/RA100Z)
+
1 + IN
2 + OUT
3 - IN/OUT
4 N.O.
5 C
1 + IN
2 + OUT
3 - IN/OUT
4 RA+
5 C
+
*4701/2 WATT RESISTOR NEEDED FOR PANEL TO RESET
D500-44-00 3 I56-2203-005
S0104-00
FIGURE 4. 4-WIRE SYSTEM TRIGGERED FROM ALARM RELAY CONTACT:
UL LISTED
ALARM
CONTROL
PANEL
DETECTOR
POWER
+
+
AUX POWER
OR
DETECTOR
POWER
INITIATING
DEVICE
CIRCUIT
+
ALARM
RELAY
(NO Contact)
PURPLE
T+
YELLOW
IN+
ORANGE
IN–
RED
PWR+
BLACK
PWR–
BROWN
OUT+
WHITE
OUT–
EOL
EOL RELAY
(SHOWN ENERGIZED)
1 + IN
2 + OUT
3 - IN/OUT
4 N.O.
5 C
1 + IN
2 + OUT
3 - IN/OUT
4 N.O.
5 C
S0105-02
FIGURE 5. CONNECTING 2WTA-B SMOKE DETECTORS TO ADEMCO CONTROLS USING RRS-MOD MODULE TRIGGERED FROM BELL/ALARM CIRCUIT:
S0106-02
FIGURE 6. CONNECTING 2WTA-B SMOKE DETECTORS TO ADEMCO CONTROLS USING RRS-MOD MODULE TRIGGERED FROM AUXILIARY RELAY:
CONNECTION DIAGRAMS WITH ADEMCO VISTA PANELS
The connection diagrams enclosed show how to connect the 2WTA-B model smoke detector to the Vista panels using the System Sensor polarity reversal relay
module (RRS-MOD). Please make sure that the smoke detectors are connected properly to the zones specified in the wiring diagrams for proper operation of the
smoke detectors.
Programming information:
• The supervisory feature for the bell cir-
cuit must be turned off. See applicable
control manual for procedure.
RRS-MOD Configuration:
• Set switch on RRS-MOD to “OFF”.
Programming information:
• Program Auxiliary relay to activate on
alarms
• Assign Auxiliary relay as an output for
zones programmed for fire alarm re-
sponse only (Types 9, 16, or 17)
RRS-MOD Configuration:
• Set switch on RRS-MOD to “ON”.